Expert settings
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2C11:001
|
High speed range: Lower limit
10 ... [20] ... 100 %
|
Definition of the lower limit of the high speed range.
–
The lower limit has a permanent hysteresis of 5 %.
|
|
|
0x2C11:002
|
High speed range: Tracking controller gain
0 ... [250] ... 65535 %
|
Gain factor for tracking the rotor position in the motor model.
|
|
|
0x2C11:003
|
High speed range: Tracking controller reset time
0.00 ... [6.00] ... 655.35 ms
|
Reset time for tracking the rotor position in the motor model.
|
|
|
0x2C11:004
|
High speed range: Tracking controller decouple time
0.00 ... [0.00] ... 655.35 ms
|
Temporal hysteresis for the switching back and forth from the open-loop controlled to the closed-loop controlled operation.
|
|
|
0x2C12:001
|
SM low speed range: Acceleration current
0 ... [100] ... 400 %
|
R.m.s. current value for acceleration processes in the lower velocity range.
–
100 % = Rated motor current (0x6075)
–
In the lower speed range and during the acceleration phase, the current setpoints of 0x2C12:001 and 0x2C12:002 are added and injected to the motor.
|
|
|
0x2C12:002
|
SM low speed range: Standstill current
0 ... [20] ... 400 %
|
R.m.s. current value for processes without acceleration (for instance standstill or constant
setpoint speed) in the lower velocity range.
–
100 % = Rated motor current (0x6075)
–
In the lower speed range and during the acceleration phase, the current setpoints of 0x2C12:001 and 0x2C12:002 are added and injected to the motor.
Note!
At the "100 %" setting, a motor current flows at standstill and at constant speed. The r.m.s. value of this motor current
is greater than the rated motor current by a factor of sqrt(2) at standstill. The reason for this is that a DC current is injected into the synchronous motor at a standstill. The correct rated motor current flows when the motor turns. |
|