Frequency and speed limitations
By limiting the maximum output frequency to ± 599 Hz, the devices are not subject to the export restrictions of the "EC-Dual-Use Regulation" (EC 428/2009).
Output frequency
The output frequency of the servo inverter is limited to a maximum value, the amount of which corresponds to the lower of the two following values:
|
|
|
|
flim
|
Maximum output frequency
|
|
fchop
|
Switching frequency 0x2939
|
|
fmax_device
|
Maximum device output frequency:
± 599 Hz |
Due to the limitation of the "Dual-Use Regulation" (EC 428/2009), values > 599 Hz do not lead to an increase of the output frequency. Please note the dead band that occurs in this case.
Speed setpoint
If servo control is used, the speed setpoint is limited depending on the number of motor pole pairs:
|
|
|
|
nlim
|
Speed limit value
|
|
flim
|
Maximum output frequency (± 599 Hz)
|
|
zp
|
Number of motor pole pairs
|
–
If the speed setpoint is limited, bit 1 ("Speed: Setpoint 1 limited") or bit 5 ("Speed: Setpoint 2 limited") is set in the Lenze status word 0x2831.
–
The behavior corresponds to the behavior which is shown when the set maximum speed 0x6080 is reached.
–
The sequence is as follows: First limit the speed to 0x6080, then limit to speed limit value nlim.
Frequency setpoint
If V/f characteristic control is used, the frequency setpoint is limited in addition to the speed setpoint.
–
If the frequency setpoint is limited, bit 10 ("Output frequency limited") is set in the Lenze status word 0x2831.