Manual "current/frequency" test mode
Preconditions for the performance
Functional description
In this test mode, three phase currents are injected into the connected motor after the inverter is enabled.
–
Adaptation of the phase currents:
|
Parameter
|
Info
|
Data type
|
|
R.m.s. value of a phase current
–
Selected in [%] based on the rated motor current.
|
INTEGER_16
|
|
|
Frequency
|
INTEGER_16
|
|
|
Starting angle
|
INTEGER_16
|
–
Reading out the present phase currents:
|
Parameter
|
Info
|
Data type
|
|
Motor current phase U
|
INTEGER_32
|
|
|
Motor current phase V
|
INTEGER_32
|
|
|
Motor current phase W
|
INTEGER_32
|
Advantages compared to the manual "voltage/frequency" test mode
–
The current cannot be set freely but is adjusted to a defined value.
–
If a synchronous motor is connected, it is possible to predict the torque.
Response of the motor during performance
–
The motor moves as a function of the set output frequency.
After the inverter has been enabled, the synchronous motor makes a jerky compensating movement
if its pole position does not correspond to the starting angle.
How to activate the manual "current/frequency" test mode:
1.
Disable inverter
Enable operation.
Enable operation. 2.
Change to the "current/frequency" test mode.
0x2825 =2
0x2825 =23.
Enable the inverter to start the test mode.
4.
To stop the test mode again: