Manual "current/frequency" test mode

Preconditions for the performance
–
The motor must rotate freely.
 
–
The inverter is error-free and in "Switched on" device state.
 
 
Functional description
In this test mode, three phase currents are injected into the connected motor after the inverter is enabled.
–
Adaptation of the phase currents:
 
Parameter
Info
Data type
R.m.s. value of a phase current
–
Selected in [%] based on the rated motor current.
 
INTEGER_16
Frequency
INTEGER_16
Starting angle
INTEGER_16
 
–
Reading out the present phase currents:
 
Parameter
Info
Data type
Motor current phase U
INTEGER_32
Motor current phase V
INTEGER_32
Motor current phase W
INTEGER_32
 
Advantages compared to the manual "voltage/frequency" test mode
–
The current cannot be set freely but is adjusted to a defined value.
 
–
If a synchronous motor is connected, it is possible to predict the torque.
 
 
Response of the motor during performance
–
The motor moves as a function of the set output frequency.
 
 
After the inverter has been enabled, the synchronous motor makes a jerky compensating movement if its pole position does not correspond to the starting angle.
 
 
How to activate the manual "current/frequency" test mode:
1.
Disable inverter Enable operation.
 
2.
Change to the "current/frequency" test mode. 0x2825 =2
 
3.
Enable the inverter to start the test mode.
 
4.
To stop the test mode again:
 
–
Disable inverter.
 
–
Change back to the CiA402 operating mode. 0x2825 = 0