General settings for test modes
Wiring check by means of manual test modes
Before starting the parameter setting of the inverter, check the motor wiring (motor connection / feedback connection) for errors and function and correct them if required:
1.
Provided that the motor is connected in correct phase relation and the rotating field frequency 0x2DDD is positive, the motor shaft rotates clockwise.
2.
An existing speed feedback in the rotor position (0x2DDE) generates a numerical value with positive counting direction. If required, take corrective measures: see the table at the end of the list.
3.
After the controller inhibit (0x6040) has been activated, the following manual test modes are available via the parameter 0x2825:
The parameters for the test modes can be adapted via the parameter . Please observe the notes in the description of the respective test mode.
|
Rotating field frequency
|
Display
|
Measure
|
|
CW
|
0...2047
|
None
|
|
2047...0
|
Correct motor connection / feedback connection
|
|
|
CCW
|
2047...0
|
None
|
|
0...2047
|
Correct motor connection / feedback connection
|
Parameter