Trouble
This device state becomes active if a serious system fault occurs. This means that the inverter is no longer able to drive the motor in a controlled way. The inverter is switched off immediately.
–
The pulse inhibit is active (pulses of the inverter are inhibited).
–
The motor is torqueless.
–
The motor brake, if available, is closed.
–
Operation is inhibited.
–
The inverter can be parameterised.
|
|
|
|
1
|
From all states
|
|
2
|
Power section inhibited (pulse inhibit)
|
|
3
|
Power section enabled
|
|
Bit pattern in the CiA status word (0x6041)
|
||||||||
|
Bit 15 ... 8
|
Bit 7
|
Bit 6
|
Bit 5
|
Bit 4
|
Bit 3
|
Bit 2
|
Bit 1
|
Bit 0
|
|
Reserved
(specific)
|
Warning active
|
Operation inhibited
|
Quick stop active
|
DC bus ready for operation
|
Fault active
|
Operation enabled
|
Switched on
|
Ready to switch on
|
|
X = state is not relevant
|
||||||||
|
X
|
X
|
0
|
X
|
X
|
1
|
0
|
0
|
0
|
This device state can only be left with the "Reset fault" command if the cause of the fault has been removed.