Device states
0x6041 (CiA status word) displays the current device status of the inverter.
|
Device status
|
Bit pattern in the CiA 402 status word (0x6041)
|
|||||||
|
Bit 7
|
Bit 6
|
Bit 5
|
Bit 4
|
Bit 3
|
Bit 2
|
Bit 1
|
Bit 0
|
|
|
Warning is active
|
Operation inhibited
|
Quick stop active
|
DC bus ready for operation
|
Fault active
|
Operation enabled
|
Switched on
|
Ready to switch on
|
|
|
X = state is not relevant
|
||||||||
|
X
|
1
|
X
|
X
|
0
|
0
|
0
|
0
|
|
|
X
|
1
|
X
|
X
|
0
|
0
|
0
|
0
|
|
|
X
|
1
|
1
|
X
|
0
|
0
|
0
|
1
|
|
|
X
|
1
|
1
|
X
|
0
|
0
|
1
|
1
|
|
|
X
|
0
|
0
|
X
|
0
|
1
|
1
|
1
|
|
|
X
|
0
|
1
|
X
|
0
|
1
|
1
|
1
|
|
|
X
|
0
|
X
|
X
|
1
|
1
|
1
|
1
|
|
|
X
|
1
|
X
|
X
|
1
|
0
|
0
|
0
|
|
Status bit 7: "Warning active"
Status bit 7 indicates a warning.
–
A warning does not cause a state change.
–
Warnings do not need to be reset.
More Lenze-specific status bits (bit 8 ... 15)
|
Device status
|
Bit pattern in the CiA 402 status word (0x6041)
|
|||||||
|
Bit 15
|
Bit 14
|
Bit 13
|
Bit 12
|
Bit 11
|
Bit 10
|
Bit 9
|
Bit 8
|
|
|
Not active
|
Brake released
|
Following error is active
|
Drive follows setpoint selection
|
Internal limitation is active
|
Target position reached
|
Control word processed successfully
|
RPDOs deactivated
|
|
|
X = state is not relevant
|
||||||||
|
Brake applied
|
X
|
0
|
X
|
X
|
X
|
X
|
X
|
X
|
|
Brake released
|
X
|
1
|
X
|
X
|
X
|
X
|
X
|
X
|
|
Active
|
0
|
X
|
X
|
X
|
X
|
X
|
X
|
X
|
|
not active
|
1
|
X
|
X
|
X
|
X
|
X
|
X
|
X
|
Detailed information on the various device states can be found in the following sections.
Parameter