Basic setting
Set the following parameters.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x605A
|
CiA: Quick stop mode
|
Device status after exiting the quick stop ramp.
|
|
|
2
|
Ramp > switch on disabled
|
Automatic change to the "Switch-on inhibited" device state.
–
The "Quick stop active [54]" status is reset to FALSE after ramp-down to standstill.
|
|
|
6
|
Ramp > quick stop active
|
The inverter remains in the "Quick stop active" device state.
–
The "Quick stop active [54]" status remains TRUE until the "Quick stop" function is activated.
|
|
|
0x605B
|
Shutdown option code
|
Defines the transition from the status "Operation enabled" to "Ready to start".
|
|
|
0
|
Disable drive function
|
0: Immediate inverter disable (standard setting)
|
|
|
1
|
Slow down on quick stop ramp and disable drive function
|
1: "Quick stop" with subsequent inverter disable.
|
|
|
0x605E
|
CiA: Response to minor faults
|
Set the transition response for slight errors.
List of minor faults:
Configuring the transition response for minor faults |
|
|
-3
|
Advanced quick stop (hoist)
|
||
|
-2
|
Advanced quick stop
|
If possible, the motor is brought to a standstill with the "quick stop" function.
If this is not possible (e.g. in the event of an encoder error), a braking torque is generated with reverse current braking or short-circuit braking.
|
|
|
0
|
No transition response
|
The motor is no longer energized.
|
|
|
2
|
Quick stop
|
The motor is brought to a standstill with the "quick stop" function.
|
|
|
0x2826
|
Timeout for error response
0 ... [4] ... 100 s
|
If the transition reaction specified in CiA: Response to minor faults is not completed within this time, the inverter changes to the 'Error' state.
The motor is no longer energized.
When the automatic brake is activated, a brake controlled by the inverter is applied.
0x2820:001 |
|
|
0x607E
|
Polarity
0 ... [0] ... 0
–
Setting can only be changed if the inverter is disabled.
|
Setting of the polarity of the position setpoint.
0 ≡ the position setpoint is interpreted as entered in 0x607A (Set position).
|
|
|
0x6085
|
Quick stop deceleration
0 ... [2147483647] ... 2147483647
|
Change in velocity used for deceleration to a standstill if quick stop is activated.
|
|
Configuring the transition response for minor faults