Configuring the transition response for minor faults

For slight errors, a transition response can be set before the 'Error' status is set.
Slight errors are predefined and cannot be changed by the user.
 
The transition response is active until standstill is reached or the timeout time has elapsed.
The inverter can still control the motor in a controlled manner.
 
List of defined slight errors
 
Event ID
Event
Severity
Configurable in
Fault - Motor temperature sensor
Warning
Fault - Motor feedback
-
Motor encoder - Communication error
-
Fault - Motor holding brake
Fault
EtherCAT - Communication error
-
EtherCAT - Sync error
-
Sync PLL - Time-out
Fault
-
 
Parameter
Address
Name / setting range / [default setting]
Information
0x605E
CiA: Response to minor faults
Set the transition response for slight errors.
-3
Advanced quick stop (hoist)
-2
Advanced quick stop
If possible, the motor is brought to a standstill with the "quick stop" function.
If this is not possible (e.g. in the event of an encoder error), a braking torque is generated with reverse current braking or short-circuit braking.
0
No transition response
The motor is no longer energized.
2
Quick stop
The motor is brought to a standstill with the "quick stop" function.
0x2826
Timeout for error response
0 ... [4] ... 100 s
If the transition reaction specified in CiA: Response to minor faults is not completed within this time, the inverter changes to the 'Error' state.
The motor is no longer energized.
When the automatic brake is activated, a brake controlled by the inverter is applied. 0x2820:001