Causes and remedies
|
Cause
|
Remedy
|
Severity/response
|
|
–
Short circuit/earth fault of motor cable
–
Capacitive charging current of the motor cable
too high.
|
–
Check motor cable.
–
Check length of the motor cable.
–
Use shorter or lower-capacitance motor cable.
|
Fault
–
The event can only be reset after a blocking time.
|
|
Blocking time: 5 s
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Short circuit of motor cable
|
Check motor cable for short circuit.
|
Fault
–
The event can only be reset after a blocking time.
|
|
Blocking time: 5 s
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor thermally overloaded, e.g. by an impermissible continuous current or by frequent or too long acceleration processes.
|
Check drive sizing.
Check the setting in the warning threshold or error threshold.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Power section overloaded.
|
Check drive sizing.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Power section overloaded.
|
Check drive sizing.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Device utilisation (ixt) too high by frequent and too long acceleration processes.
|
Check drive sizing.
|
(configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 3 s
|
||
|
Setting parameters:
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Device utilisation (ixt) too high by frequent and too long acceleration processes.
|
Check drive dimensioning.
|
Warning
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Ultimate motor current reached.
|
(configurable)
|
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Parameterized max. motor current 0x6073 > max. device current 0x2DDF:002
|
Reduce max. motor current. 0x6073
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Max. device current has been reached. (Display in 0x2DDF:002)
|
–
Select a flatter speed ramp.
–
Reduce the load.
–
Set Imax controller more dynamically. 0x2B08
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Maximum current of the axis (display in
0x2DDF:002) has been reached
too often in succession.
|
–
Select a flatter speed ramp.
–
Reduce the load.
–
Set Imax controller more dynamically.
|
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Frequent and too long acceleration processes with overcurrent.
|
Check drive sizing.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Frequent and too long acceleration processes with overcurrent.
|
Check drive sizing.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006) results from the setting of the rated mains voltage in 0x2540:001.
|
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
DC-bus voltage has fallen below the error threshold for undervoltage. The error threshold (display in 0x2540:003) results from the setting of the rated mains voltage in 0x2540:001.
|
–
Check mains voltage.
–
Check DC-bus voltage.
–
Check mains settings.
–
Check fuses.
|
Trouble
–
The event can only be reset after a blocking time.
|
|
Blocking time: 5 s
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The heatsink temperature of the power unit (display in 0x2D84:001) has exceeded the
fixed error threshold (100 °C).
–
Ambient temperature too high.
–
Fan or ventilation slots are polluted.
–
Fan is defective.
|
–
Check mains voltage.
–
Provide for a sufficient cooling of the device. In case of a 100 % load, 60 C to +70°C are normal. Display of the heatsink temperature in 0x2D84:001.
–
Clean fan and ventilation slots. If required, replace fan.
–
Reduce switching frequency 0x2939
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Sensor for the temperature monitoring of the power unit is defective. The failure of the temperature monitoring function poses the risk of overheating!
|
Hardware error: it is necessary to contact the manufacturer, since
the device must be replaced.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Warning of the heatsink fan.
|
Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Control card temperature > 100 °C
–
Ambient temperature too high
|
–
Provide for better cooling.
–
Reduce ambient temperature.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The motor temperature sensor connected to terminals X109/T1 and X109/T2 measures a too high motor temperature.
–
Motor too hot by impermissibly
high currents.
–
Motor too hot by frequent and too
long acceleration processes.
|
–
Check drive dimensioning.
–
Check motor temperature sensor and wiring.
|
Warning (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 5 s
|
||
|
Setting parameters: 0x2D49:002
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor PTC error.
|
Connect PTC or switch off monitoring.
|
Warning (configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor PTC error.
|
Connect PTC or switch off monitoring.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor temperature via load encoder higher than variable temperature limit.
|
Connect PTC or switch off monitoring.
Set a higher warning threshold (0x2D49:003) and/or error threshold (0x2D49:004).
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor PTC error.
|
Connect PTC or switch off monitoring.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
External supply voltage failed or too low.
|
–
Check external 24V voltage supply (terminal X5/24E).
–
Check mains voltage.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Warning of the internal fan.
|
Check/replace internal fan.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
CRC error in the parameter set detected.
Vendor, product code or OBD revision are different.
The parameter set is unknown.
|
Recreate parameter set.
Repeat parameter set download.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Unknown index in the parameter set.
|
Recreate parameter set.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring function of the input signal configured for analog input 1 in and has been triggered.
|
–
Check input signal at analog input 1.
–
Check configuration of the monitoring function.
|
(configurable)
|
|
Setting parameters:
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring function of the input signal configured for analog input 2 in and has been triggered.
|
–
Check input signal at analog input 2.
–
Check configuration of the monitoring function.
|
(configurable)
|
|
Setting parameters:
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Too many deviations during the pole position identification.
–
Compared to the inverter, the rated motor current is too high or too low.
|
–
Check setting of the motor data.
–
Ensure that the motor is at a standstill during the pole position identification process.
–
Ensure that the motor and inverter match each other in terms of power.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Defective encoder cable.
Defective encoder.
|
Check encoder cable.
Check encoder.
Switch off monitoring if no encoder is used.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Defective encoder cable.
Defective encoder.
|
Check encoder cable.
Check encoder.
Switch off monitoring if no encoder is used.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The communication to an encoder is disturbed.
|
Check the supply voltage of the encoder. (0x2C42:002)
Check encoder cable.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The absolute encoder position cannot be accepted as the motor rotates too fast.
|
Let the motor coast.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The communication to an encoder is disturbed.
|
Check the supply voltage of the encoder. (0x2C42:002)
Check encoder cable.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
537490307
|
0x20097383
|
Load encoder/master encoder - wrong absolute value because motor speed is too high
|
|
Cause
|
Remedy
|
Severity/response
|
|
The absolute encoder position cannot be accepted as the motor rotates too fast.
|
Let the motor coast.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Brake fault due to short circuit or cable break.
|
Check brake.
Check wiring.
|
Fault (configurable)
|
|
Setting parameters: 0x2820:006
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Motor moved too much during pole position identification.
|
Check controller settings in 0x2C62.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
"Safe Torque Off (STO)" has been activated via Safety. The movement is interrupted although the controller is still enabled.
|
Enable "Safe Torque Off (STO)" again or disable controller.
In the event of false tripping, check the wiring at terminal X1.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The motor speed has reached the error threshold for overspeed set in 0x2D44:001.
|
Adapt the maximum motor speed 0x6080 and the warning threshold or error threshold 0x2D44:001.
|
Warning (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 1 s
|
||
|
Setting parameters: 0x2D44:002
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to write a parameter that has an influence on a currently running identification or the currently activated test mode.
|
Do not change parameters until identification is complete or test mode is deactivated again.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to write a parameter that has an influence on a currently running identification.
|
Do not change parameters until identification is complete.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A failure of several motor phases has been detected.
|
–
Check wiring between inverter and motor.
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
A failure of the motor phase U has been detected.
|
–
Check wiring between inverter and motor.
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
A failure of the motor phase V has been detected.
|
–
Check wiring between inverter and motor.
–
In case of a false tripping, adapt the settings for the motor phase failure detection.
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
No response (configurable)
–
The event can only be reset after a blocking time.
|
||
|
Blocking time: 2 s
|
||
|
Setting parameters: 0x2D45:001
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to identify a resolver fault. But the V/f control without feedback system is selected as the control mode.
|
The resolver error can only be identified if a resolver is used as a feedback system. (0x2C00 = 1 or 2)
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The current speed is too low to identify the resolver error.
|
Repeat identification at higher speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to identify a resolver fault. But there is an encoder available as a feedback system.
|
The resolver error can only be identified if a resolver is used as a feedback system.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The current speed is too low to identify the resolver error.
|
Repeat identification at higher speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The current speed is too low to identify the resolver error.
|
Repeat identification at higher speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The results of the inverter error identification are not plausible.
|
Check shielding of the motor cable. Connect the shield with a surface as large as possible.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Pole position identification has been aborted.
An error has occurred during identification or the controller has been disabled.
|
Repeat pole position identification.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Reading out and accepting the HIPERFACE® data is only permitted when the controller is inhibited.
|
Disable controller before reading out.
|
Warning
|
|
|
|
537526037
|
0x2009FF15
|
No HIPERFACE® absolute value encoder as motor encoder connected - command cannot be executed
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to read out HIPERFACE® data although no HIPERFACE® encoder is connected.
No HIPERFACE® encoder is selected in 0x2C40.
|
Connect HIPERFACE® encoder.
A HIPERFACE® encoder must be selected in 0x2C40.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The HIPERFACE® encoder has a type code that is neither stored in the firmware nor corresponds to the type code set under 0x2C41:002.
|
Enter correct type code under 0x2C41:002.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
537526039
|
0x2009FF17
|
Connected HIPERFACE® motor encoder is not supported - command cannot be executed
|
|
Cause
|
Remedy
|
Severity/response
|
|
The HIPERFACE® encoder has a type code that is not stored in the firmware. Hence, no data can be detected.
|
Connect an encoder with a supported type code.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The writing of the target data has failed during operation for manual wiring control longer than the time-out time. (0x2836:005)
|
Increase timeout. (0x2836:005)
Restart manual jog dialog.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
During the automatic identification of the motor, an error has occurred.
|
–
Set motor data so that they comply
with the data on the motor nameplate.
–
Check wiring of the motor.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The HIPERFACE® encoder has a type code that is neither stored in the firmware nor corresponds to the type code set under 0x2C41:002.
|
Enter correct type code under 0x2C41:002.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
537526043
|
0x2009FF1B
|
Connected HIPERFACE® load encoder/master encoder is not supported - command cannot be executed
|
|
Cause
|
Remedy
|
Severity/response
|
|
The HIPERFACE® encoder has a type code that is not stored in the firmware. Hence, no data can be detected.
|
Connect an encoder with a supported type code.
|
Warning
|
|
|
|
537526044
|
0x2009FF1C
|
No resolver as load encoder/master encoder connected - command cannot be executed
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to identify a resolver fault. But there is an encoder available as a feedback system.
|
The resolver error can only be identified if a resolver is used as a feedback system.
|
Warning
|
|
|
|
537526045
|
0x2009FF1D
|
No HIPERFACE® absolute value encoder as load encoder/master encoder connected - command cannot be executed
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to read out HIPERFACE® data although no HIPERFACE® encoder is connected.
No HIPERFACE® encoder is selected in 0x2C50.
|
Connect HIPERFACE® encoder.
A HIPERFACE® encoder must be selected in 0x2C50.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring of the FIQ by the FPGA has triggered.
|
Connect an encoder with a supported type code.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The review of brand protection has failed.
|
Enter correct pin.
Replace device with OEM device and reprogram pin.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The specified feedforward control torque could not be built up within one second.
|
–
0x2820:009 (Starting torque source) = [0] (Last torque saved):
–
0x2820:009 (Starting torque source) = [1] (Torque in 0x2820:010):
– The set torque is too high. – Reduce torque. |
Fault
|
|
Related topics
|
|
Cause
|
Remedy
|
Severity/response
|
|
The speed error exceeds the limit from 0x2D51:001 for a time duration > 0x2D51:002.
|
Increase timeout in 0x2D51:002.
Increase limit in 0x2D51:001.
Increase gain of the speed controller.
Increase torque limit and/or current limit.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The following error exceeds the limit from 0x2D51:004 for a time duration > 0x2D51:005.
|
Increase timeout in 0x2D51:005.
Increase limit in 0x2D51:004.
Increase gain of the position controller.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Phases in the motor cable reversed.
The axis was moved manually.
Motor parameters are set incorrectly.
For synchronous motors: The pole position is set incorrectly.
For motors with holding brake: The brake was opened prematurely by an external source.
|
Check motor cabling.
Avoid manual movement.
Check number of pole pairs and motor type.
Carry out the pole position identification
Do not open the brake until you have checked the wiring.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The determined angle between rotor and resolver differs from the setting in 0x2C03:002.
The determined angle between rotor and encoder differs from the setting in 0x2C03:004.
|
Check encoder cabling.
Check motor cabling.
If appropriate, Carry out the pole position identification
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
(configurable)
|
||
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
At mains connection, a start command was already available and the automatic start at power-up is set in to "Off [0]".
|
Deactivate starting command and reset error.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Backup created via device command
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Backup restored via device command
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The short-circuit monitoring of the brake transistor has triggered.
|
Use brake resistor with a greater resistance value.
Use external brake chopper.
Use regenerative module.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring of the charge relay has responded.
|
Acknowledge error. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The mains phase monitoring has triggered.
|
Check mains connection.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The internal communication between the application and the base firmware is disturbed.
|
Restart device.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The modules in slot A and slot B cannot be combined.
|
Remove a module.
Plug a valid module combination.
|
Fault
–
The event can only be reset by mains switching.
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Initialization - Parameter value could not be written
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Write access denied with corresponding error message.
|
Evaluate parameter value based on the error message in the logbook.
Correct parameter value accordingly.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Not all parameters could be initialized.
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Not all presets could be written.
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Not all presets of the technology application could be written.
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Parameter description is missing or faulty.
|
Update boot project or device firmware.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Parameter set file is missing or faulty.
|
Update boot project or restart device.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Logbook: Corrupt restore data
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Logbook cleared
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Logbook: Timeout restoring data
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Logbook: Error restoring data
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
First boot with this firmware version
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Logbook was restored.
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Logbook: Error reading persistent data.
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The chronology of the logbook is not consistent
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
CmpLenzeErrorManagementAccess loaded without errors
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The "Application-Credit" is not sufficient for the application.
The start of the application is delayed.
|
Use SD card with sufficient "Application-Credit".
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Faulty license data was detected when the "Application-Credit" was loaded.
|
Use SD card with valid license data.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
No license data was found on the SD card when then the "Application-Credit" was loaded.
|
Use SD card with valid license data.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The "Application-Credit" is not sufficient for the boot application.
Booting is delayed.
|
Use SD card with sufficient "Application-Credit".
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in the safe brake control
|
Check the supply voltage of the brake.
Check the wiring of the brake.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, replace the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
New safety parameter set deleted
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
New safety parameter set loaded
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error accessing the safe parameter set on the SD card.
|
Reset safe parameter set in the device.
Reload safe parameter set.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safe parameter sets on the SD card and in the device are different.
|
Load a safe parameter set from the SD card into the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
No safe parameter set was found in the device.
|
Load safe parameter set into the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safe parameter set in the device is faulty.
|
Load safe parameter set into the device.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Format error in the safe parameter set
|
Reset the safe parameter set in the device and load it again.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The set safety parameters are not plausible.
|
Determine error number in 0x2115:005 and analyze it using the plausibility error table.
Eliminate error
Reload safe parameter set.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A communication error has occurred while loading the safe parameter set.
|
Check communication settings.
Check SD card.
Reload safe parameter set.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safety addresses in the device and on the SD card are different.
|
Adapt safety addresses.
Load and save the safe parameter set again.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Safe speed monitoring is faulty because the PDO version of the data protocol is incompatible.
|
Only devices with firmware > V1.0 support Extended Safety.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Unexpected FSoE command received.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Unknown FSoE command received.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
FSoE frame with invalid connection ID received.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The check of the CRC in the FSoE frames reports errors.
|
Check FSoE configuration.
Restart communication.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
FSoE watchdog elapsed.
|
Check set watchdog time in FSoE master and adapt if necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Invalid communication parameter data received.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The length of the application parameters transmitted by the FSoE master differs from the expected length.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Invalid application parameter data received.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Due to an error, FSoE was passivated.
|
Check FSoE configuration.
Reset error.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The slave address transmitted by the FSoE master differs from the slave address set in the device.
|
Check slave address in the FSoE master.
Check parameter setting in the device.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The length of the communication parameter transmitted by the FSoE master differs from the expected length.
|
Check setting of the communication parameters.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Due to an error FSoE has left the data exchange.
|
Check FSoE configuration.
Reset error.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The speed threshold "n = 0" was not reached within the stopping time.
|
Increase SS1/SS2- stopping time.
Reduce delay time in drive.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safely limited speed SLS1 has been exceeded.
|
Adapt the speed-dependent parameters in the drive.
Increase safely limited speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safely limited speed SLS2 has been exceeded.
|
Adapt the speed-dependent parameters in the drive.
Increase safely limited speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safely limited speed SLS3 has been exceeded.
|
Adapt the speed-dependent parameters in the drive.
Increase safely limited speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The safely limited speed SLS4 has been exceeded.
|
Adapt the speed-dependent parameters in the drive.
Increase safely limited speed.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A safely limited speed (SLS1-SLS4) or the maximum speed (SMS) has been exceeded.
The error was not reported within the parameterized response time.
|
Adapt the speed-dependent parameters in the drive.
Increase response time.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The drive has moved too far in the wrong direction.
|
Adapt the parameterization of the higher-level controller.
Increase 0x28BA:003 tolerance threshold
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The drive has moved too far in the wrong direction.
|
Adapt the parameterization of the higher-level controller.
Increase 0x28BA:003 tolerance threshold
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The drive has exceeded the parameterized safe maximum speed (SMS).
|
Adapt the maximum speed in the drive.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The position change during SOS is greater than the parameterized tolerance window 0x289F:001.
|
Increase tolerance window
Adapt response time of encoder monitoring.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
An attempt was made to call up a speed-based or position-based safety function although no feedback is configured.
|
Configure suitable feedback.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Ramp monitoring has responded because monitoring limits have been exceeded.
|
Adapt parameters for ramp monitoring. (0x2894)
Deactivate ramp monitoring.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The maximum permissible position change (0x28CA:001, 0x28CA:003) was exceeded.
|
Adapt parameters for SLI.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The upper or lower position limit of SLP1 has been exceeded.
|
Adapt parameters for SLP1.
Increase the distance to the position limits in the application.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The upper or lower position limit of SLP2 has been exceeded.
|
Adapt parameters for SLP2.
Increase the distance to the position limits in the application.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The upper or lower position limit of SLP3 has been exceeded.
|
Adapt parameters for SLP3.
Increase the distance to the position limits in the application.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The upper or lower position limit of SLP4 has been exceeded.
|
Adapt parameters for SLP4.
Increase the distance to the position limits in the application.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
SLP has been commissioned, but the home position is unknown.
|
Check status of the safe reference. (0x2882:006)
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The drive has exceeded the current allowed speed for PDSS.
|
Check parameters for PDSS.
Reduce speeds in the application.
Increase distance to PDSS limit values.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The drive has exceeded the currently permitted SCS creeping speed.
|
Check parameters for PDSS.
Reduce speeds in the application.
Increase distance to PDSS limit values.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
After SHom_Start, the home position was not detected within the timeout set in 0x2882:002.
|
Adapt timeout.
Check configuration of triggers for SHom_Start and SHom_Load.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The home position was deleted by acknowledging a position error or manually via 0x2114:014.
|
Execute SHom again.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The maximum permissible slip has been exceeded.
|
Evaluate slip monitoring in 0x2870:2.
Check the wear-prone drive components and replace then if necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The tolerance for the starting position has been exceeded.
|
Do not move drive components while the mains voltage is switched off.
Execute SHom again.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The tolerance for the position comparison has been exceeded.
|
Check gearbox factor and mounting direction.
Check the wear-prone drive components and replace then if necessary.
Execute SHom again.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
No safe speed could be determined. The encoder is not initialized or the status transmitted by the encoder is invalid.
|
Check encoder.
A certified motor/encoder combination must be used.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring of the safe speed via encoder is faulty.
|
Check encoder.
Check configuration of the encoder.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The monitoring of the safe speed via resolver is faulty.
|
Check encoder.
Check configuration of the encoder.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Safe speed monitoring is faulty because the device is transmitting incorrect data.
|
Check encoder.
Check configuration of the encoder.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The difference between the internally calculated speed and the speed transmitted by the encoder is too large.
|
Check configuration of the encoder.
Check gearbox factor.
Check tolerance for the deviation.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MUT - Muting function active
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MUT - Muting function completed
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Communication error. The muting function was canceled.
|
Reconnect to the device.
Restart the muting function.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The supply voltage for the HIPERFACE DSL® encoder is outside the permitted range.
|
Check the length of the system cable. The max. permitted length must not be exceeded.
Check the connections of the system cable.
Check specification of the system cable.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
HIPERFACE DSL® encoder error
|
Check the connections of the system cable.
Check details of the error in the status parameters: 0x2878:050 ... 0x2878:062 (For the meaning of the individual bits, see the documentation of the encoder manufacturer).
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
HIPERFACE DSL® communication error
|
Check the connections of the system cable.
Check details of the error in the status parameters: 0x2878:050
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Errors in safe speed monitoring (SSM) with HIPERFACE DSL® encoder
|
Check encoder configuration.
Check the connections of the system cable.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The encoder ID of the connected HIPERFACE DSL® encoder has been set to the correct value.
The error Different encoder ID has been fixed.
The status bit has been reset: 0x2878:050, bit 13
|
Check whether the encoder-axis assignment is now correct.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
805311408
|
0x300013B0
|
CTRL - IOCTL EC_IOCTL_DC_LATCH_REQ_LTIMVALS not possible in DC Latching auto read mode
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slave does not support CoE.
|
Use slave that supports CoE.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slave does not support EoE.
|
Use slave that supports EoE.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slave does not support FoE.
|
Use slave that supports FoE.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slave does not support SoE.
|
Use slave that supports SoE.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slave does not support VoE.
|
Use slave that supports VoE.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The slave status is invalid.
|
Check if slave is at least PreOperational.
Check other access rights.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
SDO protocol timeout
|
Check if timeout is set too low.
|
Warning
|
|
|
|
805311434
|
0x300013CA
|
CoE - SDO Abort 'Client/server command specifier not valid or unknown (0x05040001)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check if object exists.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check if object exists.
|
Information
|
|
|
|
805311444
|
0x300013D4
|
CoE - SDO Abort 'Number and length of objects to be mapped exceed PDO length (0x06040042)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check the length of the objects to be mapped.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
805311448
|
0x300013D8
|
CoE - SDO Abort 'Data type or length of service parameters do not match (0x06070010)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
805311449
|
0x300013D9
|
CoE - SDO Abort 'Data type does not match, service parameter too high (0x06070012)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
805311450
|
0x300013DA
|
CoE - SDO Abort 'Data type does not match, service parameter too low (0x06070013)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
805311457
|
0x300013E1
|
CoE - SDO Abort 'Data cannot be transferred/stored in application (0x08000020)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
805311458
|
0x300013E2
|
CoE - SDO Abort 'Local control - Data cannot be transferred/stored in application (0x08000021)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
805311459
|
0x300013E3
|
CoE- SDO Abort 'Actual device state - Data cannot be transferred/stored in application (0x08000022)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
805311460
|
0x300013E4
|
CoE - SDO Abort 'Object dictionary - Dynamic generation fails or object dictionary is missing (0x08000023)'
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check object properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Access denied.
|
Check access authorization.
Check file.
Check transfer properties.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
EtherCAT - State change of master successful
|
For information only. No remedy necessary.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
EtherCAT - Bus scan successful
|
For information only. No remedy necessary.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error in the network topology
|
Check network topology.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error during transmission of emergency messages.
|
Check the documentation of the slave device for this emergency message.
Note: "data: ..." shows by codes which error has occurred in which slave device/module. Detailed information about the coding of error messages can be found in the documentation of the corresponding slave device/module. |
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Master is "Operational".
At least one slave is not "Operational".
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
EtherCAT cable connected
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Network cabling is faulty.
|
Check network cabling.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Network cabling is faulty.
|
Check network cabling.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
At least one slave is in the "Error" state.
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A slave reports an error.
|
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The connection to the slave is interrupted.
The slave does not respond.
The slave is no longer available.
|
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
CoE access denied.
|
Analyze detailed error message in the logbook.
Check object properties.
Check transfer properties.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
DC slaves are 'in-sync'
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The DC deviation is outside the permissible limits.
|
Check slave status.
Check slave properties.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal message
|
For information only. No remedy necessary.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A slave has been removed from the network topology.
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A slave has been added to the network topology.
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The network topology has been changed.
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
"Border Close" has been executed on the port.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
IDN - Write error.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
IDN - read error.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
SoE - emergency transfer error.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
SoE - emergency request.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
SoE - transfer error during a notification.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
SoE - notification has been requested.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
FoE has been aborted.
|
Check file.
Check transfer properties.
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Bus scan state
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
No edge.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Remote API diagnosis port - Connection established
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Remote API diagnosis port - Connection disconnected
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Client has registered with cookie.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Client logged out from cookie.
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The number of detected slaves differs from the number of expected slaves.
|
Analyze detailed error message in the logbook.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The slave is not configured
|
Check slave status.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Communication interruption
|
Check slave status.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Detected slave status differs from expected slave status.
|
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Wrong response to the request.
|
Check slave status.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Wrong response to the request.
|
Check slave status.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The command cannot be executed
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Read error
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The command cannot be executed
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
RAP - Invalid parameter size
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Order error
|
Analyze detailed error message in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Possibly the network cable is missing.
|
Check slave status.
Check network topology.
|
Information
|
|
|
|
805312101
|
0x30001665
|
ecatSetTargetState cannot set EtherCAT master into target state, master is busy (time-out)
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Incorrect setting.
|
Check bus cycle.
Check sync period.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The bus scan was aborted due to timeout.
|
Analyze detailed error message in the logbook.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The vendor ID could not be checked.
|
Analyze detailed error message in the logbook.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The product code could not be checked.
|
Analyze detailed error message in the logbook.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The revision could not be checked.
|
Analyze detailed error message in the logbook.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The vendor ID could not be checked.
|
Analyze detailed error message in the logbook.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
A surplus device was detected at the end of the bus.
|
Analyze detailed error message in the logbook.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error counter resetted
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
All slaves 'Operational' again
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
WKC error
|
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Frame response error
|
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Not all slaves have been set to 'Operational'.
|
Analyze detailed error message in the logbook.
Check slave status.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Too many emergency messages.
|
Check if slave sends too many emergency messages.
Eliminate cause.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
New configuration loaded
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
New configuration loaded, no slaves defined
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
See related entries in the logbook.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
New configuration loaded from slaves EEPROM
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Bus configuration error
|
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Network cabling is faulty.
|
Check network cabling.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slaves cannot be set to 'Pre-Operational'.
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Operational' could not be set.
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Master not initialized.
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Network cabling is faulty.
|
Check network cabling.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Incorrect setting.
|
Check bus cycle.
Check sync period.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Master - Set 'Operational' takes some time...
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
See related entries in the logbook.
Check slave status.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slave error
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Master - Set 'Operational' aborted by reset command
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Master cannot be stopped.
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Slave error
|
See related entries in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Master - Shutdown failed
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Start Download Service
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Download Service done
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - "Modular Machine Configuration" is active.
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - Service started
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - Service stopped
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
|
Check MMC configuration file.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - File does not exist
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
|
Check MMC configuration file.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - parsing of file successful
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
|
Check MMC configuration file.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
|
Check MMC configuration file.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
|
Check MMC configuration file.
Analyze detailed error message in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Incorrect alias address.
|
Check SSA addresses of the slaves.
Analyze detailed error message in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Double alias address.
|
Check SSA addresses of the slaves.
Analyze detailed error message in the logbook.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - No configuration checks
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Internal error
|
Restart the device. If the error persists, contact the manufacturer.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Check MMC configuration file.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Check MMC configuration file.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - No valid service active
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - Address assignment successful
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - Address assignment done
|
For information only. No remedy necessary.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC - Address assignment error, writing address by CoE
|
For information only. No remedy necessary.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
MMC configuration file is faulty.
Network topology is faulty.
|
Analyze detailed error message in the logbook.
Check MMC configuration file.
Check network topology.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Service request rejected because master not in "Init" status
|
Check status of the master.
Set status of the master to "Init".
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
EtherCAT Distributed Clock (DC) not activated.
|
Activate DC mode.
|
Warning
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
EtherCAT communication interrupted.
|
–
Check bus cable.
–
Increase watchdog time.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Wrong Sync Manager setting from EtherCAT master
|
–
Check node.
–
Check the sequence of the nodes.
–
Check bus cable.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Wrong Sync Manager setting from EtherCAT master
|
–
Check node.
–
Check the sequence of the nodes.
–
Check bus cable.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Wrong Sync Manager setting from EtherCAT master
|
–
Check node.
–
Check the sequence of the nodes.
–
Check bus cable.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Unknown index in the PDO mapping
|
Correct PDO mapping.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The index cannot be mapped as PDO.
|
Correct PDO mapping.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
More than 64 objects are mapped.
|
Reduce number of objects in PDO mapping.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
PDO mapping is faulty.
|
Check PDO mapping.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The object to be mapped is already used by the PLC.
|
Remove object from mapping.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
EtherCAT Sync0 has failed.
–
PDO was sent or received too late.
|
–
Check in the EtherCAT master configuration whether Distributed Clock is activated.
–
Restart EtherCAT configuration.
–
Shift PDO reception time via user shift time.
–
Increase telegram failure error counter:
0x10F1:002 |
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Error during state change Pre-Operational → Safe-Operational:
–
EtherCAT Sync0 has failed.
–
The Sync0 jitter is too high.
|
–
Check DC deviation in EtherCAT master.
–
Restart EtherCAT configuration.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The requested Sync0 cycle is outside the supported limits.
|
Correct Sync0 cycle.
|
Fault
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
Within the time-out period for explicit messages, which has been parameterised by the scanner, no "explicit message" was received.
–
The connection to the scanner has been interrupted.
–
Failure of an explicit connection.
|
–
Check cables and terminals.
–
Plug network cables into the Ethernet port.
–
Check the requested package interval (RPI) of the explicit connection.
–
Increase time limit for explicit messages in the scanner.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
–
EtherNet/IP: the maximum permissible time-out period for the CIP communication set in has been exceeded.
–
Modbus TCP/IP: the maximum permissible time-out period for the TCP communication set in has been exceeded.
|
–
Check cables and terminals.
–
Connect network cable.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Time-out during cyclic data reception, e.g. due to an interrupted communication link to the master or missing cyclic data.
|
–
Check wiring of the network.
–
Eliminate EMC interferences.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The communication partner has interrupted the cyclic data exchange.
|
–
Check wiring of the network.
–
The slave must receive new parameterisation and configuration files by the master, in order to be able to exchange data again.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The initialisation of the communication stack has been interrupted due to an incorrect address setting or communication configuration.
|
Check master/slave configuration and restart the devices.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
The cyclic process data received are invalid.
|
Check cyclic process data sent by the master.
|
(configurable)
|
|
Setting parameters:
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Communication with the safety option could not be initialized correctly.
|
Check safe parameter set.
|
Information
|
|
|
|
Cause
|
Remedy
|
Severity/response
|
|
Communication with the safety option is disturbed.
|
Check status of the safety option.
|
Information
|
|
|
Device overload monitoring (ixt)