Overcurrent monitoring

This function monitors the instantaneous value of the motor current and serves to protect the motor from irreversible damage. Overcurrent monitoring is effective for all motor control modes.
 
NOTICE
With an incorrect parameterization, the maximum permissible motor current may be exceeded in the process.
Possible consequences: Irreversible damage of the motor
Avoid motor damages by using the overcurrent monitoring function as follows:
▶
The setting of the threshold for the overcurrent monitoring in 0x2D46:001 must be adapted to the connected motor.
 
▶
Set the maximum current of the inverter in 0x6073 much lower than the threshold for overcurrent monitoring for a dynamic limitation of the motor current.
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D46:001
Overcurrent monitoring: Threshold
0.0 ... [5.4] ... 3000.0 A
Associated event ID:
–
537469828 | 0x20092384 - Ultimate motor current reached
 
0x2D46:002
Overcurrent monitoring: Response
Selection of the response to the triggering of motor current monitoring.
Associated event ID:
–
537469828 | 0x20092384 - Ultimate motor current reached
 
0
No response
1
Warning
2
Trouble