Motor overload monitoring (i²xt) Motor temperature monitoring
In order to record and monitor the motor temperature, a PTC thermistor (single sensor according to DIN 44081 or triple sensor according to DIN 44082) or thermal contact (normally-closed contact) can be connected to the terminals T1 and T2. This measure helps to prevent the motor from being destroyed by overheating.
Preconditions
–
The inverter can only evaluate one PTC thermistor! Do not connect several PTC thermistors in series or parallel.
–
If several motors are actuated on one inverter, thermal contacts (NC contacts) (TCO) connected in series are to be used.
–
To achieve full motor protection, an additional temperature monitoring function with a separate evaluation must be installed.
–
By default, a wire jumper is installed between terminals X109/T1 and X109/T2, which must be removed when the PTC thermistor or thermal contact (TCO) is connected.
Details
If 1.6 kΩ < R < 4 kΩ at terminals X109/T1 and X109/T2, the monitoring function will be activated; see functional test below.
–
If the monitoring function is activated, the response set in 0x2D49:002 will be effected.
–
The setting 0x2D49:002 = 0 deactivates the monitoring function.
If a suitable motor temperature sensor is connected to the terminals X109/T1 and X109/T2 and the response in 0x2D49:002 is set to "Fault [3]", the response of the motor overload monitoring may be set other than "Fault [3]" in .
Motor overload monitoring (i²xt)
Motor overload monitoring (i²xt) Functional test
Connect a fixed resistor to the PTC input:
–
R > 4 kΩ : The monitoring function must be activated.
–
R < 1 kΩ : The monitoring function must not be activated.
Details
If 1.6 kΩ < R < 4 kΩ at terminals X109/T1 and X109/T2, the monitoring function will be activated; see functional test below.
–
If the monitoring function is activated, the response set in 0x2D48:002 will be effected.
–
The setting 0x2D48:002 = 0 deactivates the monitoring function.
If a suitable motor temperature sensor is connected to the terminals X109/T1 and X109/T2 and the response in 0x2D48:002 is set to "Fault [3]", the response of the motor overload monitoring may be set other than "Fault [3]" in 0x2D4B:003.
Motor overload monitoring (i²xt)
Motor overload monitoring (i²xt) Functional test
Connect a fixed resistor to the PTC input (T1/T2):
–
R > 4 kΩ : The monitoring function must be activated.
–
R < 1 kΩ : The monitoring function must not be activated.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2D48:002
|
PTC temperature sensor monitoring: Error response
|
Setting of a response for PTC temperature monitoring.
|
|
|
0
|
No response
|
||
|
1
|
Fault > CiA402
|
||
|
2
|
Warning
|
||
|
0x2D49:001
|
Motor temperature monitoring: Temperature sensor type
|
Selection of the motor temperature sensor used.
|
|
|
0
|
KTY83-110
|
||
|
1
|
KTY83-110+2xPTC 150 °C
|
||
|
2
|
KTY84-130
|
||
|
3
|
Specific characteristic
|
||
|
4
|
Reserved
|
||
|
5
|
PT1000
|
||
|
6
|
PT1000+2xPTC 150 °C
|
||
|
0x2D49:002
|
Motor temperature monitoring: Response
|
Selection of the response to the triggering of the motor temperature monitoring.
Associated event IDs:
–
537477904 | 0x20094310 - Motor overtemperature
–
537478016 | 0x20094380 - Fault - Motor temperature sensor
|
|
|
0
|
No response
|
||
|
1
|
Warning
|
||
|
0x2D49:003
|
Motor temperature monitoring: Warning threshold
-3276.8 ... [145.0] ... 3276.7 °C
|
Setting of the warning threshold for motor temperature monitoring.
The warning threshold is reset with a hysteresis of 5 °C.
|
|
|
0x2D49:004
|
Motor temperature monitoring: Error threshold
-3276.8 ... [155.0] ... 3276.7 °C
|
Setting of the error threshold for motor temperature monitoring
The warning threshold is reset with a hysteresis of 5 °C.
|
|
|
0x2D49:005
|
Motor temperature monitoring: Actual motor temperature
–
Read only: x.x °C
|
Display of the current motor temperature.
|
|
|
0x2D49:006
|
Motor temperature monitoring: Spec. characteristic temperature grid point 1
0.0 ... [25.0] ... 255.0 °C
|
Parameter for the specific thermal sensor characteristic (0x2D49:001 = 3).
|
|
|
0x2D49:007
|
Motor temperature monitoring: Spec. characteristic temperature grid point 2
0.0 ... [150.0] ... 255.0 °C
|
||
|
0x2D49:008
|
Motor temperature monitoring: Spec. characteristic resistance grid point 1
0 ... [1000] ... 30000 Ω
|
||
|
0x2D49:009
|
Motor temperature monitoring: Spec. characteristic resistance grid point 2
0 ... [2225] ... 30000 Ω
|
||
|
0x2DDF:007
|
Axis information: Function of X109
–
Read only
|
||
|
0
|
None
|
||
|
10
|
HIPERFACE DSL® (OCT)
|
||
|
20
|
PTC
|
||