Motor phase failure detection
The motor phase failure detection function can be activated for both synchronous
and asynchronous motors.
In the Lenze setting, monitoring is not activated!
Preconditions
Motor phase failure detection during operation is suitable for applications
which are operated with a constant load and speed. In other cases,
transient processes or unfavourable operating points can cause erroneous triggering to occur.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2D45:001
|
Motor phase failure detection: Response - Motor phase 1
|
Selection of the response following the detection of a motor phase failure during operation.
Associated event IDs:
–
537526025 | 0x2009FF09 - Motor phase missing
–
537526026 | 0x2009FF0A - Motor phase failure phase U
–
537526027 | 0x2009FF0B - Motor phase failure phase V
–
537526028 | 0x2009FF0C - Motor phase failure phase W
|
|
|
0
|
No response
|
||
|
1
|
Warning
|
||
|
2
|
Trouble
|
||
|
0x2D45:002
|
Motor phase failure detection: Current threshold
1.0 ... [5.0] ... 10.0 %
|
||
|
0x2D45:003
|
Motor phase failure detection: Voltage threshold
0.0 ... [10.0] ... 100.0 V
|
Voltage threshold for motor phase monitoring
for the VFC control mode (0x2C00 = 6).
–
The monitoring function is triggered if the motor current exceeds the rated motor current-dependent current threshold for longer than 20 ms. Rated motor current 0x6075
–
In case of the V/f characteristic control, the voltage threshold is considered additionally for the motor phase failure detection. If the motor voltage is higher than the voltage threshold, monitoring is combined with the motor current.
|
|
|
0x2D45:004
|
Motor phase failure detection: Response - Motor phase 2
|
Selection of the response following the detection of a motor phase failure directly after controller enable.
|
|
|
0
|
No response
|
||
|
1
|
Fault > CiA402
|
||
|
2
|
Trouble
|
||
Severity