Imax controller

Defining the behaviour at the current limit (Imax controller)
The maximum output current or the current limit is defined by the 0x6073 "max. current" parameter. In case of the V/f characteristic control, an Imax controller is implemented for complying with this limit. If the motor current exceeds the set maximum current, the Imax controller is activated.
–
The Imax controller changes the rotating field frequency so that the motor current does not exceed the current limit. In motor mode, the frequency is reduced and in generator mode it is increased.
 
–
The gain and reset time of the Imax controller can be parameterised.
 
 
Optimising the Imax controller
The automatic calculation serves to determine starting parameters of the Imax controller which are sufficient for many applications. Thus, an optimisation is not required for most of the applications.
The automatic calculation is made via the parameter 0x2822:019 = 1.
 
The parameters of the Imax controller must be adapted if
–
a power control is implemented with great moments of inertia.
Recommendation:
Step 1: increase reset time in 0x2B08:002
Step 2: reduce gain in 0x2B08:001
 
–
vibrations occur with V/f characteristic control during the operation of the Imax controller.
Recommendation:
Step 1: increase reset time in 0x2B08:002
Step 2: reduce gain in 0x2B08:001
 
–
overcurrent errors occur due to load impulses or too high acceleration/deceleration ramps.
Recommendation:
Step 1: reduce reset time in 0x2B08:001
Step 2: increase gain in 0x2B08:002
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B08:001
V/f Imax controller: Gain
0.000 ... [0.001] ... 1000.000 Hz/A
Gain factor Vp of the Imax controller.
0x2B08:002
V/f Imax controller: Reset time
1.0 ... [100.0] ... 2000.0 ms
Reset time Ti of the Imax controller.