ASM field controller

For motors with great rotor time constants or small rotor resistances, very high gain factors are calculated. Since the setting range of the field controller is limited to the double rated magnetising current, the field control loop in the case of these motors tends to a two-point response when the values calculated are entered.
The automatic calculation is made via the parameter 0x2822:016 = 1.
 
Starting from a calculated gain factor of approx. 1000 A‍/‍Vs, do not set the full value anymore.
Example
Calculated value: 10000 A‍/‍Vs
Setting: 3000 A‍/‍Vs
 
Calculation of the gain
 
 
Calculation of the reset time
 
Parameter
Symbol
Description
Dimension unit
Vp
Field controller gain
A/Vs
Tn
Field controller reset time
s
Lh
Mutual motor inductance (ASM)
H
Rr
Motor rotor resistance (ASM)
Ω
-
Tcurrent controller
Equivalent time constant of the current control loop = 0.0005 s
-
Tr
Motor rotor time constant
-
KPath
Gain of the control path
-
Lr
Motor rotor resistance (ASM)
H
 
Parameter
Address
Name / setting range / [default setting]
Information
0x29C0:001
Field controller settings: Gain
0.00 ... [165.84] ... 500000.00 A/Vs
Gain factor Vp of the field controller.
0x29C0:002
Field controller settings: Reset time
1.0 ... [15.1] ... 6000.0 ms
Reset time Tn of the field controller.