ASM field weakening controller

Since the controlled system gain changes with the speed, the field weakening controller is corrected via the speed.
The automatic calculation is made via the parameter 0x2822:017 = 1.
 
Calculation of the gain
 
 
Calculation of the reset time
 
Parameter
Symbol
Description
Dimension unit
Vp
Gain of the field weakening controller
Vs / A
-
VPath_Fs
Gain of the control path
-
P
Number of pole pairs
rpm 
-
ntransition
Speed at which the field weakening is approximately initiated.
Tn
Reset time of the field weakening controller
s
-
TEF
Filter time constant of the field control loop
TFilter
Filter time constant for the required voltage
s
-
Tr
Motor rotor time constant
-
Lr
Motor rotor resistance (ASM)
Lh
Mutual motor inductance (ASM)
H
Lss
Motor stator leakage inductance (ASM) or motor leakage inductance (SM)
H
Rr
Motor rotor resistance
Ω
 
Parameter
Address
Name / setting range / [default setting]
Information
0x29E0:001
Field weakening controller settings: Gain (ASM)
0.000 ... [0.000] ... 2147483.647 Vs/V
Gain factor Vp of the field weakening controller.
0x29E0:002
Field weakening controller settings: Reset time (ASM)
1.0 ... [2000.0] ... 240000.0 ms
Reset time Tn of the field weakening controller.
0x29E1
Field weakening controller Field limitation
5.00 ... [100.00] ... 100.00 %
Field limitation of the field weakening controller.