Speed controller
The speed controller is automatically set when the motor has been selected from the motor catalogue:
The automatically calculated settings for the speed controller enable an optimal control behaviour for typical load requirements.
Manual post-optimisation of the speed controller
1.
Setting of the gain
Set the proportional gain Vp in parameter 0x2900:001.
Set the proportional gain Vp in parameter 0x2900:001.
a.
Specify speed setpoint.
b.
Increase parameter until the drive gets unstable (observe engine noise).
0x2900:001
0x2900:001c.
Reduce parameter until the drive runs stable again.
0x2900:001
0x2900:001d.
Reduce the parameter to approx. half the value.
0x2900:001
0x2900:0012.
Setting of the reset time
Set the reset time Tn in parameter 0x2900:002.
Set the reset time Tn in parameter 0x2900:002.
a.
Reduce parameter until the drive gets unstable (observe engine noise).
0x2900:002
0x2900:002b.
Increase parameter until the drive runs stable again.
0x2900:002
0x2900:002c.
Increase parameter to approx. double the value.
0x2900:002
0x2900:0023.
Setting of the rate time
Set the rate time Td in parameter 0x2900:003.
Set the rate time Td in parameter 0x2900:003.
a.
Increase parameter during operation until an optimal control mode is achieved.
0x2900:003
0x2900:003Automatically calculated settings for the speed controller
We recommend a manual post-optimisation for the optimal operation.
The function for automatically calculating the gain and reset time is executed via the parameter
0x2822:014
. The following equations apply to a "rigid" system.
–
For elastic systems and systems with batches, the determined gain must be reduced.
–
The moment of inertia required for the calculation is the sum of the moment of inertia of the motor and the load mass inertias transformed to the motor side.
Equation for calculating the gain
Equation for calculating the reset time
|
rotating field frequencyrotating field frequencyrotating field frequencyParameter
|
Symbol
|
Description
|
Dimension unit
|
|
Vp
|
Speed controller gain
|
Nm / rpm
|
|
|
-
|
J
|
Moment of inertia = Jmotor + sum (Jload)
|
kgm2
|
|
-
|
a
|
Measure for the phase reserve
(recommendation: a = 4
≡ 60° phase reserve) |
|
|
TFilter
|
Filter time constant - actual speed value
|
s
|
|
|
-
|
Tcurrent controller
|
Equivalent time constant of the current control loop = 0.0005 s
|
s
|
|
Tn
|
Reset time - speed controller
|
s
|
Special case of the linear motor
In this case, a re-calculation from a linear system to a rotary system must be made. Therefore, via the feedback system a degree of freedom results for the determination of the number of pole pairs. For a rotary system, the number of pole pairs specifies the ratio of electrical and mechanical revolution, the number of encoder increments being defined via one mechanical revolution. In the case of a linear system, the user is free to decide for which length he or she wants to specify the number of encoder increments. Usually, the number of increments is given for a pole distance or for the total length of the linear scale. If the number of increments = "number of increments for one pole distance" is selected, a motor with the number of pole pairs zp = 1 is created. The effective moment of inertia for a linear motor can be calculated according to the following equations. With this J value, the equations shown above can be used to calculate the speed controller gain and reset time.
Equation for calculating the effective moment of inertia
|
Parameter
|
Symbol
|
Description
|
Dimension unit
|
|
-
|
s
|
Length on which the specification for the number of encoder increments is based (e.g. per pole distance or total length).
|
m
|
|
-
|
2
τ Pole pair |
Pole distance of the permanent magnets, pole pair width
|
m
|
|
-
|
J
|
Moment of inertia = JForcer + JSlide + JLoad
|
kgm2
|
|
-
|
m
|
Moving mass = mForcer + mSlide + mLoad
|
kg
|
Parameter