Monitoring

Three different EtherCAT monitoring systems are available.
–
Monitoring for cable interruption
 
–
For distributed clocks (DC):
 
–
Sync0 monitoring
 
–
PDO telegram failure detection
 
 
 
Monitoring for cable interruption
This monitoring generally checks whether the EtherCAT cable is interrupted. Monitoring is not configurable and works with and without distributed clocks".
Behavior in the event of a cable interruption:
–
The inverter changes to the "Safe-Operational" state.
 
–
The inverter triggers a parameterizable error response.
 
–
Error response: 0x605E
 
–
Error code: 0x30018181
 
 
 
Sync0 monitoring for DC
This monitoring checks whether the Sync0 signals are generated correctly in time in the inverter when the inverter is in the "Operational" state.
The following is monitored:
–
After "Pre-Operational" has changed to "Safe-Operational", the generation of Sync0 pulses has to be started within 5 seconds.
 
–
The change from "Safe-Operational" to "Operational" without Sync0 signals being generated.
 
–
No more Sync0 signals are detected for the duration of the double Sync0 cycle time.
 
Error behavior:
–
The inverter changes to the "Safe-Operational" state.
 
–
The inverter triggers a parameterizable error response.
 
–
Error response: 0x605E
 
–
Error code: 0x30018700
 
–
AL status code: 0x32
 
 
 
PDO telegram failure detection for DC
This monitoring checks whether an EtherCAT PDO telegram has arrived between two Sync0 signals (Sync Manager 2 Event).
For this purpose, the inverter has an internal error counter for PDO telegram failures:
–
Each failed PDO telegram increases the counter by the value "3".
 
–
Each correctly received PDO telegram decreases the counter by the value "1".
 
–
Monitoring is configurable. 0x10F1:002
 
Error behavior:
–
The inverter changes to the "Safe-Operational" state.
 
–
The inverter triggers a parameterizable error response.
 
–
Error response: 0x605E
 
–
Error code: 0x30018701
 
 
Recommendation: Set 0x10F1:002 ≥ 4.
Thus one failed PDO telegram is tolerated, two PDO telegram failures in a row are forbidden.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x10F1:001
Error settings: Local error reaction
An error response takes place exclusively via the inverter.
2
Device specific state
0x10F1:002
Error settings: Sync error counter limit
0 ... [20] ... 100
Setting for PDO frame failure detection.
When the internal telegram failure error counter reaches the value set here, the inverter changes to the "Safe-Operational" state and causes an error (CiA402 error code 0x8700).