Event reset

Depending on the severity of the event, the event must be reset so that inverter operation can continue.
Resetting is possible only when the cause of triggering the event has been eliminated.
 
Options to reset events:
–
Via buttons in the Engineering Tools in the "Diagnostics" tab
 
–
Via network with bit 7 in CiA 402 control word 0x6040
 
–
Via parameter 0x2841
 
 
Notes:
–
Certain events can only be reset by mains switching.
 
–
Certain events (e. g. earth fault or short circuit of the motor phases) may cause a blocking time.
 
–
The error can be reset only after the blocking time has elapsed.
 
–
An active blocking time is displayed via bit 14 in the inverter status word. 0x2831.
 
 
–
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2840
Error reset time
–
Read only: x ms
 
Display of the remaining blocking time until the event can be reset.
0x2841
Reset error
0 ... [0] ... 1
1 = reset error
0x2022:035
Device commands: Restart Device
Parameter for interaction with engineering tools.
0
Off / ready
Only status feedback
1
On / start
Execute device command
2
In progress
Only status feedback
3
Action cancelled
4
No access
5
No access (Device disabled)