Status LEDs
The LEDs "RDY" and "ERR" show the current safety status:
Fig. 1: Position of the RDY and ERR LEDs
DANGER!Inaccurate status information possible due to LEDs.
LEDs are not reliable status displays.
Possible consequences: Death or severe injuries
▶
Only use LEDs for general diagnostics during commissioning or troubleshooting.
▶
Do not use LEDs as status displays.
|
LED "RDY" (yellow)
|
|
Status
|
Meaning
|
|
off
|
|
-
|
No status message active.
|
|
blinking yellow 2 Hz
|
SOS active
|
|
|
|
blinking yellow 1 Hz
|
Service status
|
Transfer of parameter set requested.
|
|
LED "RDY" (yellow)
|
LED "ERR" (red)
|
Status
|
Meaning
|
|
on
|
blinking red 1 Hz
|
Restart acknowledgement requested
|
During startup, a modified parameter set was detected in the "Init" state.
|
|
blinking red 2 Hz
|
During startup, a changed safety address was detected in the "Init" state.
|
||
|
blinking red
|
During startup, a changed assignment between OCT encoder and inverter was detected in the "Init" state.
|
|
|
LED "ERR" (red)
|
Status
|
Meaning
|
|
|
off
|
-
|
The device is working correctly.
|
|
blinking red 2 Hz
|
Safety bus error
|
Communication via the safety bus is not established:
–
There is no valid configuration.
–
The start-up has not been completed yet.
|
|
|
blinking red 1 Hz
|
Safety technology error
|
One of the following errors has been detected:
–
A monitoring device has been activated.
–
An acknowledgeable error is active.
|
|
LED "RDY" (yellow)
|
LED "ERR" (red)
|
Status
|
Meaning
|
|
blinking yellow
|
blinking red
|
Critical system error
|
–
"Lock-out" (CPU stopped)
–
STO is active.
–
If the system error occurs again after switching the 24 V supply, the device is defective. It must be replaced.
|
Acknowledgement with confirmation button S82