Calculation of the maximum response times

For the calculation of the response time to the request of a safety function, the overall system must be taken into account:
–
Response time of the connected safety sensors.
 
–
Input delay of the safety inputs.
 
–
Internal processing time.
 
–
Deceleration times, braking times, and stopping times from the parameterized safety functions.
 
–
When using a feedback system, the response time of encoder monitoring 0x2878:004
 
–
Safety bus:
 
–
Monitoring time for cyclic services.
 
–
Monitoring time in the safety PLC.
 
–
Processing time in the safety PLC
 
 
–
Delay times due to further components.
 
The ETG FSoE protocol specification contains formulas for calculating the maximum response time in fault-free operation and in the event of a fault.
 
In the "Application Knowledge Base", Lenze provides an Excel table as a calculation aid. This can be used to easily calculate the reaction times.
 
 
Please note the following:
The variables for the individual response times are named differently in the documentation for the c250-S safety controller than in the FSoE protocol specification of the ETG.
In the following graphics, the differences are marked with "Lenze" and "ETG".
Definition of the single response times
Name Lenze
Name ETG
Description
Comment
T_Sensor
T_S
Processing time of the sensor until the signal is available at the interface.
See technical data of the sensor
T_InputFilter
Parameterized filter time of the safe input.
T_Input
T_I
Processing time of the safe input.
E.g. safety I/O module, FSoE sensor or inverter.
See technical data
T_WDInput
T_WD_In
Monitoring time parameterized in the safety PLC (c250-S) for the safe input module.
E.g. safety I/O module, FSoE sensor or inverter.
T_EtherCAT
T_Com
EtherCAT cycle time
T_FSoE
Processing time of the communication, depending on the EtherCAT cycle time
The documentation of the c250-S specifies max. 3 x T_EtherCAT.
The ETG FSoE protocol specification specifies max. 2 x T_Com.
It depends on the application which factor can be used. Factor 3 means improved availability of secure communications.
T_SafetyPLC
T_L
Processing time of the safety PLC (c250-S).
Corresponds to the set cycle time of the safety application.
T_Output
T_O
Processing time of the safe output.
E.g. safety I/O module or inverter.
See technical data
T_WDOutput
T_WD_Out
Monitoring time parameterized in the safety PLC (c250-S) for the safe output module.
E.g. safety I/O module or inverter.
T_Aktor
T_A
Processing time of the actuator.
See technical data of the actuator
 
Maximum response time with error-free communication
 
Note the different factors for calculating the processing time of the communication:
The documentation of the c250-S specifies max. 3 x T_EtherCAT.
The ETG FSoE protocol specification specifies max. 2 x T_Com.
It depends on the application which factor can be used. Factor 3 means improved availability of secure communications.
 
 
Fig. 1: Maximum response time with error-free communication without Safe Brake Control (SBC)
Fig. 2: Maximum response time with error-free communication with Safe Brake Control (SBC)
Calculation of the maximum response time with error-free communication
Max. response time without SBC
Max. response time with SBC
T_InConn
2 × T_S
2 × T_S
+
2 × T_I
+
2 × T_I
+
2 × T_Com (3 × T_Com)
+
2 × T_Com (3 × T_Com)
+
2 × T_L
+
2 × T_L
T_OutConn
+
2 × T_L
+
2 × T_L
+
2 × T_Com (3 × T_Com)
+
2 × T_Com (3 × T_Com)
+
2 × T_O
+
2 × T_O
+
2 × T_A
=
T_SFR
=
T_SFR
 
Response time in case of communication interruption
The FSoE watchdog time T_WD is included in the calculation of the maximum response time in case of communication interruption.
The FSoE watchdog time T_WD can be calculated according to the formula in the ETG FSoE protocol specification.
The processing times in the individual subsystems and the processing time of the communication are included in this calculation. In addition, a reserve of 20% is added.
 
Fig. 3: FSoE watchdog time
Depending on the input module and the output module used, the calculation may result in different values.
The higher value must always be used for further calculation to improve the availability of secure communication.
 
Calculation of the FSoE watchdog time
Input module
Output module
2 × T_I
+
4 × T_Com (6 × T_Com)
+
4 × T_Com (6 × T_Com)
+
2 × T_L
+
2 × T_L
+
2 × T_O
+
ΔT (20 %)
+
ΔT (20 %)
=
T_WD_In
=
T_WD_Out
 
Calculation of the maximum response time in case of communication interruption in the input module
Max. response time without SBC
Max. response time with SBC
T_InConn_wc
2 × T_S
2 × T_S
+
T_WD_In
+
T_WD_In
T_OutConn
+
2 × T_L
+
2 × T_L
+
2 × T_Com (3 × T_Com)
+
2 × T_Com (3 × T_Com)
+
2 × T_O
+
2 × T_O
+
2 × T_A
=
T_SFR _wc (In)
=
T_SFR _wc (In)
Calculation of the maximum response time in case of communication interruption in the output module
Max. response time without SBC
Max. response time with SBC
T_InConn
2 × T_S
2 × T_S
+
2 × T_I
+
2 × T_I
+
2 × T_Com (3 × T_Com)
+
2 × T_Com (3 × T_Com)
+
2 × T_L
+
2 × T_L
T_OutConn_wc
2 × T_L
2 × T_L
+
T_WD_Out
+
T_WD_Out
+
2 × T_A
=
T_SFR _wc (Out)
=
T_SFR _wc (Out)
Calculation of the maximum response time in case of communication interruption for the entire system
Max. response time without SBC
Max. response time with SBC
T_SFR _wc
=
max {T_SFR _wc (In); T_SFR _wc (Out)}
=
max {T_SFR _wc (In); T_SFR _wc (Out)}