Status messages
The status feedback described below takes place via non-secure interfaces. The status feedback must not be used to control other safety functions!
Status feedback via network
The CiA status word (0x6041) contains the status of the STO function according to the following truth table. This parameter object can be read via non-secure network interfaces.
|
Status
|
Status feedback
|
||
|
Safe input X1
|
Inverter device state
|
CiA status word
(Object 0x6041)
|
|
|
SIA
|
SIB
|
Bit 15
|
|
|
LOW
|
LOW
|
STO active
|
0
|
|
LOW
|
HIGH
|
Impermissible state (drive disabled)
|
0
|
|
HIGH
|
LOW
|
0
|
|
|
HIGH
|
HIGH
|
Drive enabled
|
1
|