Internal torque limits

The torque limits currently effective in the drive are set in the parameters and Positive torque limit and Negative torque limit.
–
Positive torque limit0x500A:128
 
–
Negative torque limit0x500A:129
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x500A:013
Actual torque
–
Read only: x.xx Nm
 
0x500A:128
Positive torque limit
-3276.8 ... [200.0] ... 3276.7 %
Positive torque limit
–
100 % = rated motor torque 0x6076
 
0x500A:129
Negative torque limit
-3276.8 ... [200.0] ... 3276.7 %
Negative torque limit
–
100 % = rated motor torque 0x6076
 
0x6076
Rated motor torque
0.001 ... [0.600] ... 100000.000 Nm
–
Setting can only be changed if the inverter is disabled.
 
The rated motor torque to be set here serves as a reference value for different parameters with a setting/display of a torque value in percent.
Example:
–
Rated motor torque = 1.65 Nm
 
–
Max. torque 0x6072 = 250 % Rated motor torque = 4.125 Nm
 
0x6077
Actual torque
–
Read only: x.x %
 
Display of the actual torque.
–
100 % = Rated motor torque 0x6076
 
0x60E0
Positive torque limit
0.0 ... [100.0] ... 3276.7 %
Positive torque limit source for speed control with torque limitation.
–
100 % = Rated motor torque 0x6076
 
–
The value is taken from the application: 0x500A:128.
 
0x60E1
Negative torque limit
0.0 ... [100.0] ... 3276.7 %
Negative torque limit source for speed control with torque limitation.
–
100 % = Rated motor torque 0x6076
 
–
The value is taken from the application: 0x500A:129.