External torque limits
The external torque limit is defined via the External torque limit parameter.
0x5040:017
0x5040:017The external torque limit is activated with bit 22 of the Control signal parameter.
0x5040:010
0x5040:010Bit 22 of the Status signals parameter indicates whether the external torque limit is active.
0x5040:110 Bit 22
0x5040:110 Bit 22As long as the external torque limit remains inactive, the two parameters Positive torque limit and Negative torque limit define what torque limits apply.
The function mode of the external torque limit is set via the Impact of external speed limit parameter.
The following settings are possible via this parameter:
Fig. 1: 0x5040:003 = 0: Setting affects the positive and negative torque limit
Fig. 2: 0x5040:003 = 1: Setting affects the positive torque limit
Fig. 3: 0x5040:003 = 2: Setting affects the negative torque limit
Static torque limits can be defined for the axis, which are active during normal operation. The definition is done via the parameters:
The torque limits can be deactivated in the technology application and can be replaced by alternative torque limits.
The alternative torque limits are set in the technology application via a control word
in the inverter and via the L_MC1P_SetTorqueLimit function block in the Controller-based Automation.
in the inverter and via the L_MC1P_SetTorqueLimit function block in the Controller-based Automation.
If the set torque limits in the technology application have been changed, this is indicated in the Status word parameter in bit 20.
0x500A:005 Bit 20
0x500A:005 Bit 20 The torque limits currently effective in the drive are displayed in the parameters Positive torque limit source and Negative torque limit source.
0x60E0
0x60E1
0x60E0
0x60E1 If no external torque limits are activated, the torque limits Positive torque limit and Negative torque limit are active.
The external torque limits are configured via the External torque limit parameter and activated via the Control signals parameter.
The function mode of the external torque limits is set via the Effective direction of external torque limit parameter.
The Effective direction of external torque limit parameter sets whether the External torque limit parameter has an impact on the positive torque limit, the negative torque limit, or on both torque limits.
Parameter