External torque limits

The external torque limit is defined via the External torque limit parameter. 0x5040:017
The external torque limit is activated with bit 22 of the Control signal parameter. 0x5040:010
Bit 22 of the Status signals parameter indicates whether the external torque limit is active. 0x5040:110 Bit 22
As long as the external torque limit remains inactive, the two parameters Positive torque limit and Negative torque limit define what torque limits apply.
–
Positive torque limit 0x500A:128
 
–
Negative torque limit 0x500A:129
 
The function mode of the external torque limit is set via the Impact of external speed limit parameter.
The following settings are possible via this parameter:
Fig. 1: 0x5040:003 = 0: Setting affects the positive and negative torque limit
Fig. 2: 0x5040:003 = 1: Setting affects the positive torque limit
Fig. 3: 0x5040:003 = 2: Setting affects the negative torque limit
 
Static torque limits can be defined for the axis, which are active during normal operation. The definition is done via the parameters:
–
Positive torque limit 0x500A:128
 
–
Negative torque limit 0x500A:129
 
The torque limits can be deactivated in the technology application and can be replaced by alternative torque limits.
The alternative torque limits are set in the technology application via a control word
in the inverter and via the L_MC1P_SetTorqueLimit function block in the Controller-based Automation.
If the set torque limits in the technology application have been changed, this is indicated in the Status word parameter in bit 20. 0x500A:005 Bit 20
The torque limits currently effective in the drive are displayed in the parameters Positive torque limit source and Negative torque limit source. 0x60E0 0x60E1
 
If no external torque limits are activated, the torque limits Positive torque limit and Negative torque limit are active.
–
Positive torque limit 0x500A:128
 
–
Negative torque limit 0x500A:129
 
The external torque limits are configured via the External torque limit parameter and activated via the Control signals parameter.
The function mode of the external torque limits is set via the Effective direction of external torque limit parameter.
The Effective direction of external torque limit parameter sets whether the External torque limit parameter has an impact on the positive torque limit, the negative torque limit, or on both torque limits.
–
Positive torque limit 0x60E0
 
–
Negative torque limit 0x60E1
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x500A:128
Positive torque limit
-3276.8 ... [200.0] ... 3276.7 %
Positive torque limit
–
100 % = rated motor torque 0x6076
 
0x500A:129
Negative torque limit
-3276.8 ... [200.0] ... 3276.7 %
Negative torque limit
–
100 % = rated motor torque 0x6076
 
0x5040:017
External torque limit
0.00 ... [0.00] ... 21474836.47 %
Value of the external torque limit.
Reference: Rated motor torque 0x6076
0x5040:115
Actual torque
-214748.3648 ... [0.0000] ... 214748.3647 Nm
Display of the actual torque
0x6076
Rated motor torque
0.001 ... [0.600] ... 100000.000 Nm
–
Setting can only be changed if the inverter is disabled.
 
The rated motor torque to be set here serves as a reference value for different parameters with a setting/display of a torque value in percent.
Example:
–
Rated motor torque = 1.65 Nm
 
–
Max. torque 0x6072 = 250 % Rated motor torque = 4.125 Nm
 
0x6077
Actual torque
–
Read only: x.x %
 
Display of the actual torque.
–
100 % = Rated motor torque 0x6076
 
0x60E0
Positive torque limit
0.0 ... [100.0] ... 3276.7 %
Positive torque limit source for speed control with torque limitation.
–
100 % = Rated motor torque 0x6076
 
–
The value is taken from the application: 0x500A:128.
 
0x60E1
Negative torque limit
0.0 ... [100.0] ... 3276.7 %
Negative torque limit source for speed control with torque limitation.
–
100 % = Rated motor torque 0x6076
 
–
The value is taken from the application: 0x500A:129.