Setting

Please note when combining the Safely-limited speed (SLS) and Safe direction (SDI) functions:
–
The parameterized directions of movement must be coordinated.
 
–
The start delays for SLS and SDI must be coordinated:
 
–
SLS and SDI are requested at the same time.
 
 
The mode of action of the parameters can be found in the dialog box for the function in the "Safety parameter list" in the engineering tool used.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x28B8:001
SDI: SDIpos - Source SD-In
–
Safety parameter (+Safety parameter list+)
 
Selection of a safe input as a trigger source for the function.
0
Disabled
1
SD-In1
2
SD-In2
3
SD-In3
4
SD-In4
0x28B8:002
SDI: SDIneg - Source SD-In
–
Safety parameter (+Safety parameter list+)
 
Selection of a safe input as a trigger source for the function.
0
Disabled
1
SD-In1
2
SD-In2
3
SD-In3
4
SD-In4
0x28B9:001
SDI: SDIpos - Source S-Bus
–
Safety parameter (+Safety parameter list+)
 
Selection of the safety bus as the trigger source for the function.
0
Disabled
1
Activated
0x28B9:002
SDI: SDIneg - Source S-Bus
–
Safety parameter (+Safety parameter list+)
 
Selection of the safety bus as the trigger source for the function.
0
Disabled
1
Activated
0x28BA:001
SDI: Monitoring standard operation
–
Safety parameter (+Safety parameter list+)
 
Setting of a permanent monitoring function for the direction of movement in normal operation.
0
Both directions enabled
1
Positive direction enabled
2
Negative direction enabled
0x28BA:002
SDI: Delay time
0 ... [0] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Safe monitored time from activation to switching on the monitoring SDIpos or SDIneg.
0x28BA:003
SDI: Tolerance threshold
0 ... [8192] ... 327680 incr.
–
Safety parameter (+Safety parameter list+)
 
Setting of the tolerance threshold specifying by how many increments the motor may move in the direction locked by SDI.
The incremental position value is related to the motor encoder.
0x28BA:004
SDI: Error response
–
Safety parameter (+Safety parameter list+)
 
Response when a wrong direction of movement of the motor is detected.
0
STO
1
SS1
2
SS2
0x28BA:005
SDI: Maximum change of position
–
Read only: x incr.
 
Maximum occurred position change in the not allowed direction when SDI is active.
0x28BB:001
SDI: "SDIpos observed" - Output
–
Safety parameter (+Safety parameter list+)
 
Selection of the safe output for the "SDIpos" feedback.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic
0x28BB:002
SDI: "SDIneg observed" - Output
–
Safety parameter (+Safety parameter list+)
 
Selection of the safe output for the "SDIneg" feedback.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic