Device overload monitoring (ixt)

The inverter calculates the ixt utilization in order to protect itself against thermal overload. In simple terms: a higher current or an overcurrent that continues for a longer time causes a higher ixt utilization.
 
DANGER!
Uncontrolled motor movements by pulse inhibit.
When the device overload monitoring function is activated, pulse inhibit is set and the motor has no torque. A load that is connected to motors without a holding brake may therefore cause uncontrolled movements! Without a load, the motor will coast.
Possible consequences: Death or severe injuries
▶
Only operate the inverter under permissible load conditions.
 
 
 
Details
The device overload monitoring function primarily offers protection to the power section. Indirectly, also other components such as filter chokes, circuit-board conductors, and terminals are protected against overheating. Short-time overload currents followed by recovery periods of smaller current utilisation are permissible. The monitoring function during operation checks whether these conditions are met, taking into consideration that higher switching frequencies and lower stator frequencies as well as higher DC currents cause a greater device utilization.
–
If the total utilization exceeds the total warning threshold set in 0x2D40:008 (default setting: 95 %), the inverter outputs a warning.
 
–
If the device utilization exceeds the permanent error threshold 100 %, the inverter is disabled immediately and generates an error message.
 
–
The device overload can be obtained from the planning manual.
 
 
The total utilization is determined via various timers that become active at different high currents. As a result, it can happen that individual timers still display 0% utilization, although the total utilization is already significantly higher.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D40:001
Device utilisation ixt: Power unit actual utilisation
–
Read only: x %
 
Display of the power module utilisation.
0x2D40:002
Device utilisation ixt: Power unit warning threshold
0 ... [95] ... 101 %
If the device utilisation exceeds the threshold set, the inverter outputs a warning.
0x2D40:003
Device utilisation ixt: Power unit error threshold
–
Read only: x %
 
If the power module utilisation exceeds the displayed threshold, the inverter outputs a warning.
0x2D40:004
Device utilisation ixt: Device actual utilisation
–
Read only: x %
 
Display of the current device utilisation.
0x2D40:005
Device utilisation ixt: Device warning threshold
0 ... [95] ... 101 %
0x2D40:006
Device utilisation ixt: Device error threshold
–
Read only: x %
 
If the device utilisation exceeds the displayed threshold, the device outputs an error.
0x2D40:007
Device utilisation ixt: Actual total utilisation
–
Read only: x %
 
Display of the current total device utilisation.
0x2D40:008
Device utilisation ixt: Total utilisation warning threshold
0 ... [95] ... 101 %
If the total utilisation exceeds the set threshold, the device outputs a warning.
0x2D40:009
Device utilisation ixt: Total utilisation error threshold
–
Read only: x %
 
If the total utilisation exceeds the displayed threshold, the device outputs an error.