Set load adjustment

CAUTION!
If the load adjustment is too high, the motor current may increase in idle state and the motor may overheat!
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B07:001
Load adaption: Direction of rotation
–
Setting can only be changed if the inverter is disabled.
 
Selection for adapting the characteristic as a function of the load in case of CW and CCW rotation.
0
Passive load
1
Active load CCW
2
Active load CW
0x2B07:002
Load adaption: Load adaption value
0.00 ... [20.00] ... 200.00 %
Setting of the load adaptation in [%] proportionally to the rated motor torque to obtain an appropriately "rigid" drive behavior even after start-up.
–
For starting torque = rated motor torque, a load adaptation of 50 % is suitable for most applications.