Activate voltage vector control (Imin controller)

The voltage vector control is used if a comparatively high starting torque must be provided. This function ensures that the required motor current is maintained in the lower speed range.
 
NOTICE
The boost function described here adds to the Set voltage boost function. 
Only set one of the two "boost" functions.
▶
Recommendation: torque increase in the lower speed range
 
▶
Take into consideration that the increased current at low speeds also entails higher heat losses of the motor.
 
 
 
–
The voltage vector control is activated by defining a current setpoint.
 
–
For the automatic calculation of the control parameters, the "Calculate Imin controller" function is provided via parameter .
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B04
V/f boost controller - current setpoint
0.00 ... [0.00] ... 500.00 A
Setting of the current setpoint for the voltage vector control.
–
The setting "0.00 A" deactivates the voltage vector control.
 
–
When defining the current setpoint, we recommend you to provide a reserve of 20 % in order to largely exclude a "stalling" of the motor caused by unexpected additional loads.
 
–
Example for starting torque = rated motor torque: Set the current setpoint to approx. 120 % of the load current.
 
0x2B05:001
V/f boost controller settings: Gain
0.00 ... [148.21] ... 750.00 V/A
Setting of the gain for the voltage vector control.
0x2B05:002
V/f boost controller settings: Reset time
0.01 ... [3.77] ... 2000.00 ms
Setting of the reset time for the voltage vector control.
0x2B05:003
V/f boost controller settings: Dynamic current setpoint
0.00 ... [0.00] ... 500.00 A