Compensate inverter influence to output voltage
In addition to the exact motor voltage, a detailed knowledge of the stator resistance is required. If the flying restart process does not work as desired, slightly adapt the setting of the stator resistance in the 0x2C01:002 object. Bit 1 in the Lenze control word 0x2830 serves to block a flying restart process.Flying restart circuit
The "flying restart" function serves as a protective function against high compensation currents. High compensation currents can occur in the V/f characteristic control if the drive is not at standstill at the time the inverter is enabled. The "flying restart" function detects the motor speed by means of a test current and uses this information to define the frequency setpoint.
CAUTION!If the "flying restart" function is deactivated and the inverter is not enabled at standstill, the output voltage and the output frequency do not match the current motor speed.
High compensation currents may flow! First the drive is braked towards 0 Hz to be then accelerated again!
▶
Ensure that the drive is at standstill before the inverter is enabled.
Flying restart process
If this function is active, the flying restart process starts after the inverter is enabled.
1.
The inverter reports the started flying restart process to the Controller via bit 8 in the Lenze status word0x2831.
2.
If a speed is found, it is reported to the Controller via bit 9 in the Lenze status word.
3.
The Controller reports to the inverter via bit 0 in the Lenze control word 0x2830 that the detected speed has been accepted. As long as this is not the case, no further flying restart process is possible.
Parameter setting
The flying restart algorithm needs a motor voltage as exact as possible. Thus, a previous detection of the inverter error characteristic is absolutely necessary.
The flying restart process involves a control loop, the controller parameter 0x2BA3 of which must be adapted to the motor. The automatic calculation is made with the parameter
0x2822:022.
0x2822:022.The actual flying restart process can be adjusted via the following parameters:
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2BA0
|
Activate flying restart
|
Activation of the additional "flying restart" function.
If the "flying restart" function is activated ("1: on") and the inverter disable is deactivated, a flying restart process is automatically started for determining the current motor speed if the following conditions are met:
–
The V/f characteristic control is set as motor control.
–
The CiA402 mode is selected as drive mode.
–
The "flying restart" function is not blocked via bit 2 in the Inverter control word (0x2830).
–
No DC-injection braking is active.
–
No motor phase failure has been identified.
|
|
|
0
|
Off
|
||
|
1
|
On
|
||
|
2
|
Without acknowledge or blocking
|
||
|
0x2BA1
|
Flying restart circuit
0 ... [15] ... 100 %
|
||
|
0x2BA2
|
Start frequency
-600.0 ... [20.0] ... 600.0 Hz
|
Start frequency of flying restart algorithm
–
If it is foreseeable at which frequency the motor can be restarted on the fly, set the frequency here.
|
|
|
0x2BA3
|
Integration time
1 ... [600] ... 60000 ms
|
Integration time of the angle controller
–
The default setting is adapted for medium-power machines.
–
A guide value for the integration time can be calculated as a function of the motor power with the following equation: Ti = 1.1 µ/W * Rated power (0x2C01:006) + 9.4 ms
–
For accelerating the search process, this guide value can be reduced.
–
If the flying restart frequency oscillates too much, increase the integration time again.
–
A longer integration time extends the time for a flying restart of the drive.
|
|
|
0x2BA4
|
Minimum deviation
0.00 ... [5.00] ... 90.00 °
|
Setting of the minimum permissible deviation.
|
|
|
0x2BA5
|
Delay time
0 ... [0] ... 10000 ms
|
In order to prevent the start of a flying restart process if the controller inhibit time is too short, a minimum active time for the inverter disable can be set here in order that a flying restart process will be started.
As a pulse inhibit > 500 ms causes a controller inhibit, this also applies to pulse inhibit.
|
|
|
0x2BA6:001
|
Result: Determined speed [rpm]
–
Read only: x rpm
|
Display of the determined speed in [rpm].
|
|
|
0x2BA6:002
|
Result: Determined speed [n unit]
–
Read only: rpm
|
Display of the determined speed in [n unit].
|
|