Manual "current pulse" test mode
The stator resistance and the stator inductance of the inverter must be adapted to the electrical characteristics of the motor. For an experimental adjustment, the manual
"Current pulse" test mode can be used.
This test mode is provided for adjusting the current controller in the "Servo control for synchronous motor/asynchronous motor" operating mode and is not suitable for adjusting the Imax controller in the "V/f characteristic control (VFC)" operating mode!
In the manual "Current pulse" test mode, setpoint step-changes are applied to the current controller input subsequent to controller enable. The step responses must then either be recorded using an oscilloscope and a clamp-on ammeter, or using the oscilloscope function of the inverter. It is the objective to optimise the two "Gain" and "Reset time" current controller parameters by evaluating the step responses so that a speedy current characteristic is achieved, which, if possible, is free of harmonics.
In the case of motors with single pole windings, satisfactory results are possibly only achieved with a current-dependent correction of the current controller parameters. For this purpose, a characteristic is stored in the inverter, which describes the current dependance of the stator leakage inductance and which tracks the current controller gain.
After the inverter has been enabled, the synchronous motor makes a jerky compensating movement if its pole position does not correspond to the starting angle.
The motor phase U is energized with a DC current the level of which is determined via the following equation.
In motor phases V and W, half of this DC current flows (negative; from the motor).
The following parameters are relevant to the calculation:
–
Manual test mode: setpoint current
0x2835:001
0x2835:001–
Motor rated current
0x6075
0x6075–
Read only: current phase U
0x2D83:002
0x2D83:002–
Read only: current phase V
0x2D83:003
0x2D83:003–
Read only: current phase W
0x2D83:004
0x2D83:004Conditions for the execution
–
The motor must be parameterised completely.
–
The motor utilisation (I²xt) monitoring must be parameterised and switched to active.
Motor overload monitoring (i²xt)
Motor overload monitoring (i²xt) –
The motor must rotate freely.
–
The inverter is error-free and switched on.
–
The rotor of synchronous motors must be in the pole centre during the test. For some synchronous motors, it might be required
to align and lock the rotor in the pole centre.
–
Using the manual test mode "current/frequency" is useful for a one-time alignment of the rotor
with the following settings:
R.m.s. value = 70 ... 100 %; frequency = 0 Hz; starting angle = 0°
Manual "current/frequency" test mode
R.m.s. value = 70 ... 100 %; frequency = 0 Hz; starting angle = 0°
Manual "current/frequency" test mode –
Fixation by means of the holding brake or the use of external fixation aids
Responses of the motor during performance
Remove the mechanical fixation after the current controller has been adjusted!
The motor usually aligns itself only once with the first controller enable.
How to adjust the current controller by means of the manual test mode "current pulse":
–
Disable inverter.
–
Calculate start parameters for the inverter based on the parameterised motor data.
–
The automatic calculation is made via the parameter 0x2822:013.
–
You can determine the start parameter manually.
–
Change to the "current pulse" test mode.
0x2825 = 3
0x2825 = 3–
Set the setpoint current for the manual test mode.
0x2835:001
0x2835:001–
Enable the inverter for a short while to start the test mode.
–
Measure the step response of the motor current in the motor phase U by means of an oscilloscope and a clamp-on ammeter.
–
Evaluate the step response.
–
Adjust the gain and the reset time of the inverter.
–
Repeat steps 1 ... 6 until the optimum step response of the motor current has been reached.
–
Exit the test mode:
–
For permanent saving: save changed current controller parameters.