PROFINET
PROFINET® (Process Field Network) is a real-time capable network based on Ethernet.
–
PROFINET® is a registered trademark and patented technology licensed by the PROFIBUS & PROFINET International (PI) user organization.
–
Detailed information on PROFINET can be found on the web page of the user organization: https://www.profibus.com
–
PROFINET transmits, between the IO-Devices and a IO-Controller (PLC), parameter data, configuration data, diagnostic data, alarm messages, and process data.
–
The data is transmitted as a function of its time-critical behavior via corresponding communication channels.
–
The device is implemented as a PROFINET IO-Device in a PROFINET RT network.
–
The PROFINET connections are realized as standard RJ45 sockets.
–
Information about the dimensioning of a PROFINET network can be found in the configuration document.
Preconditions
–
The inverter is equipped with the "PROFINET" network module.
Connection via RJ45 sockets X256 and X257 with commercially available standard Ethernet cable from CAT 5/5e.
Connection via RJ45 sockets X256 and X257 with commercially available standard Ethernet cable from CAT 5/5e.
–
Selection of the technology application in the inverter with parameter
0x4000 > 1.
0x4000 > 1.More information about connections can be found on the Internet:
www.profibus.com
à
PROFINET Cabling and Interconnection TechnologyDevice description files for Lenze products can be found on the Internet:
www.Lenze.com
www.Lenze.com
à
Downloads à
Product-related Application Knowledge Base articlesTypical topologies
|
Line
|
Tree
|
|
|
|
|
Ring
|
|
|
|
C
|
IO controller
|
SW
|
Switch SCALANCE (MRP capable)
|
|
D
|
IO device
|
R
|
Redundant domain
|
Technical data
|
Range
|
Values
|
|
Communication profile
|
PROFINET
|
|
Communication medium/cable type
|
S/FTP (Screened Foiled Twisted Pair, ISO/IEC 11801 or EN 50173), CAT5e Standard Ethernet (acc. to IEEE 802.3), 100Base-TX (Fast Ethernet)
|
|
Network topology
|
Line, star, and tree
|
|
Type within the network
|
PROFINET I/O-Device (slave)
|
|
Max. cable length
|
100 m between two devices
|
|
I/O data (PDO data)
|
–
Max. 244 PDOs: freely configurable, regardless of their direction (In, Out, In/Out)
–
Max. 1024 input bytes and max. 1024 output bytes
–
Scaling:
bytes: 1, 2, 4, 8, 16, 32, 64, 128, 192, 256, 320, 384, 448, 512, 1024 Word: 1, 2, 4, 8, 16, 32, 64, 128, 192, 256, 320, 384, 448, 512 –
The combination of I/O data in one slot is possible.
|
|
Communication type
|
PROFINET I/O cyclic
|
|
Functions
|
–
Transmission of cyclic process data
–
Context Management via CL-RPC (Connectionless Remote Procedure Call)
The Context Management Protocol is used for establishing and terminating connections, requesting resources, exchanging configuration and diagnostic information, uploading/downloading records. –
Setpoint/actual comparison of the PROFINET configuration
|
|
Special features in the Lenze automation system
|
Configuration in the »PLC Designer«:
–
No submodules
–
Only one device instance is supported.
No support of
–
acyclic write and read requests
–
DCP (Discovery and basic Configuration Protocol)
–
RTP (Real-Time Transport Protocol) over UDP (User Datagram Protocol)
–
Multicast communication
–
Process/diagnostic alarms
–
Generic diagnostics, channel diagnostics
|
|
Minimum cycle time
|
2 ms
|