PROFINET

PROFINET® (Process Field Network) is a real-time capable network based on Ethernet.
 
–
PROFINET® is a registered trademark and patented technology licensed by the PROFIBUS & PROFINET International (PI) user organization.
 
–
Detailed information on PROFINET can be found on the web page of the user organization: https://www.profibus.com
 
–
PROFINET transmits, between the IO-Devices and a IO-Controller (PLC), parameter data, configuration data, diagnostic data, alarm messages, and process data.
 
–
The data is transmitted as a function of its time-critical behavior via corresponding communication channels.
 
–
The device is implemented as a PROFINET IO-Device in a PROFINET RT network.
 
–
The PROFINET connections are realized as standard RJ45 sockets.
 
 
–
Information about the dimensioning of a PROFINET network can be found in the configuration document.
 
 
Preconditions
–
The inverter is equipped with the "PROFINET" network module.
Connection via RJ45 sockets X256 and X257 with commercially available standard Ethernet cable from CAT 5/5e.
 
–
Selection of the technology application in the inverter with parameter 0x4000 > 1.
 
More information about connections can be found on the Internet:
www.profibus.com 
à
PROFINET Cabling and Interconnection Technology
 
 
Device description files for Lenze products can be found on the Internet:
www.Lenze.com 
à
Downloads
à
Product-related Application Knowledge Base articles
 
 
Typical topologies
Line
Tree
Ring
C
IO controller
SW
Switch SCALANCE (MRP capable)
D
IO device
R
Redundant domain
 
Technical data
Range
Values
Communication profile
PROFINET
Communication medium/cable type
S/FTP (Screened Foiled Twisted Pair, ISO/IEC 11801 or EN 50173), CAT5e Standard Ethernet (acc. to IEEE 802.3), 100Base-TX (Fast Ethernet)
Network topology
Line, star, and tree
Type within the network
PROFINET I/O-Device (slave)
Max. cable length
100 m between two devices
I/O data (PDO data)
–
Max. 244 PDOs: freely configurable, regardless of their direction (In, Out, In/Out)
 
–
Max. 1024 input bytes and max. 1024 output bytes
 
–
Scaling:
bytes: 1, 2, 4, 8, 16, 32, 64, 128, 192, 256, 320, 384, 448, 512, 1024
Word: 1, 2, 4, 8, 16, 32, 64, 128, 192, 256, 320, 384, 448, 512
 
–
The combination of I/O data in one slot is possible.
 
Communication type
PROFINET I/O cyclic
Functions
–
Transmission of cyclic process data
 
–
Context Management via CL-RPC (Connectionless Remote Procedure Call)
The Context Management Protocol is used for establishing and terminating connections, requesting resources, exchanging configuration and diagnostic information, uploading/downloading records.
 
–
Setpoint/actual comparison of the PROFINET configuration
 
Special features in the Lenze automation system
Configuration in the »PLC Designer«:
–
No submodules
 
–
Only one device instance is supported.
 
No support of
–
acyclic write and read requests
 
–
DCP (Discovery and basic Configuration Protocol)
 
–
RTP (Real-Time Transport Protocol) over UDP (User Datagram Protocol)
 
–
Multicast communication
 
–
Process/diagnostic alarms
 
–
Generic diagnostics, channel diagnostics
 
Minimum cycle time
2 ms