onboard EtherCAT - Operation as master or slave on the system bus

EtherCAT® (Ethernet for Controller and Automation Technology) is an Ethernet-based fieldbus system which fulfils the application profile for industrial realtime systems.
 
–
EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
 
–
Detailed information on EtherCAT can be found on the web page of EtherCAT Technology Group (ETG): http://www.ethercat.org
 
–
Information about the sizing of an EtherCAT network can be found in the configuration document.
 
 
The inverter is equipped with an onboard EtherCAT connection that can be used in two variants:
–
Connection of the inverter as Distributed Clocks (DC)-capable EtherCAT slave for process data and safety data under a standard EtherCAT motion control
 
–
Connection of the inverter to the EtherCAT system bus.
 
 
The EtherCAT system bus offers the simple possibility of synchronizing up to 16 inverters without additional motion control via the onboard EtherCAT connection. The physically first inverter on the system bus is the EtherCAT master, the other system bus nodes are slaves. The system bus is configured automatically (plug & play).
 
Preconditions
–
Only inverters of the i950 series are connected to the system bus.
 
–
A maximum of 16 nodes including the master can be connected via the system bus.
 
–
No further accessories are connected to the system bus.
 
–
The inverters are not parameterised as CiA 402 motion drives, i.e. selection of a technology application: 0x4000 > 1
 
The technology application set is not checked.
 
 
Details
–
The inverter can act as a system bus master or system bus slave.
 
–
The system bus is prepared, i. e. a configuration is not required.
 
–
The master assigns an identical master value to all system bus nodes (slaves).
 
–
The »EASY Starter« is sufficient ...
 
–
to parameterise the devices in the network;
 
 
–
to configure the process data individually.
 
 
 
–
If further EtherCAT-compliant devices are to be used in addition to the inverters, the bus configuration must be adapted to the »PLC Designer«.
 
 
–
Detailed information regarding the adaptation of the EtherCAT configuration with the »PLC Designer« can be found here:
 
–
Online help »EASY Starter«/»PLC Designer«, topic "Controller-based Automation EtherCAT"
 
–
Communication manual "Controller-based Automation EtherCAT" (PDF)
 
 
 
System bus topology
X246
System bus interface EtherCAT IN
x247
System bus interface EtherCAT OUT
X6
Ethernet NRT interface
A
EtherCAT system bus
B
Engineering PC
M
System bus master
S1 ... 15
System bus slaves 1 ... 15