Commissioning
Commissioning can be subdivided as follows:
–
Initial commissioning in which at least the system bus master must be determined.
–
System bus change, in which slave devices are added or removed subsequently.
Preconditions
–
The inverter is linked in the system bus network (max. 16 devices) as EtherCAT master or EtherCAT slave.
See "system bus topology" under:
onboard EtherCAT - Operation as standard EtherCAT slave
See "system bus topology" under:
onboard EtherCAT - Operation as standard EtherCAT slave –
The entire wiring has been checked for completeness, short circuit and earth fault.
–
All system bus nodes are supplied with voltage and are switched on.
–
An Engineering PC with installed »EASY Starter« is connected to the master.
Parameterisation required
Set and activate master functionality at the 1st inverter in the system bus network:
1.
Setting: 0x2371:009 = 1
2.
Save parameter settings.
Saving the parameter settings
Saving the parameter settings 3.
Restart inverter.
Device command: 0x2022:035 = 1
Device command: 0x2022:035 = 1
The master function of the 1st inverter is now activated.
The cyclic master value and the individual process data are set via the technology application (0x4000) of the system bus master.
The cyclic master value and the individual process data are set via the technology application (0x4000) of the system bus master.
The 0x2371:009 parameter does not need to be set for the slave devices. The slave functionality is already preset with the value "0".
Select and configure technology applications:
1.
Select a technology application (unequal to "CiA 402").
Selection with: 0x4000
Selection with: 0x4000
2.
Optionally set the "IO configuration" with: 0x4001
3.
Save parameter settings.
Saving the parameter settings
Saving the parameter settings The technology applications of the inverter are now set.
The technology application in the system bus master provides the master value. The slave devices are FAST slaves (process slaves) as well and follow the master value of the process master.
Start system bus:
1.
Restart system bus master (1st inverter).
Device command: 0x2022:035 = 1
Device command: 0x2022:035 = 1
All devices currently found at the system are assigned and addressed to the corresponding devices in the device tree of the system bus master according to their physical order at the bus. See "Addressing of the system bus nodes under:
Basic setting and options
The number of devices at the system bus may be lower than the number of devices in the device tree of the system bus master.
All devices at the system bus are set to the "Operational" bus state when they have been identified as system bus nodes.
Basic setting and options The number of devices at the system bus may be lower than the number of devices in the device tree of the system bus master.
All devices at the system bus are set to the "Operational" bus state when they have been identified as system bus nodes.