Basic setting and options
Addressing the system bus nodes
The first device in the system bus network is always active as EtherCAT master.
In addition, this device is also an internal EtherCAT slave, which e. g. provides a DC master (Distributed Clocks).
The slave devices at the system bus are addressed via their active EtherCAT station address.
This address is assigned by the master while the system bus is initialised:
–
The internal slave in the master device has the address "1001".
–
The first slave in the network has the address "1002".
–
The second slave in the network has the address "1003" etc.
Master/slave functionality
The 0x2371:009 parameter is used to set the functionality of the system bus interface of the inverter (EtherCAT master/slave).
Parameter