Process data transfer
In the system bus network …
–
the setpoint process data (master to slave) are set via the system bus master inside the technology application;
–
the actual process data (slave to master) is set via the slave device.
Data mapping
All inverter i950 slave devices have a fixed generic data mapping. This data mapping enables the use of the slave devices with an i950 inverter as system bus master and with other EtherCAT-based master control systems (PLC).
–
The process data is set to 8 double words (32 bytes) for each direction.
–
Output data direction: From Master to Slave.
–
Input data direction: From Slave to Master.
–
This fixed data mapping is automatically activated as master for an i950 inverter.
–
The process data is transmitted cyclically in a 1 ms cycle between the master and the slaves.
–
The process data transfer is synchronised by the "Distributed Clocks" EtherCAT mechanism.
–
A i950 master device provides the DC master via the internal slave.
–
The data in the slaves is accepted synchronously with the PLC program in the master.
–
All slaves are synchronised with a reference clock, the so-called "DC master".