Process data transfer

In the system bus network …
–
the setpoint process data (master to slave) are set via the system bus master inside the technology application;
 
–
the actual process data (slave to master) is set via the slave device.
 
 
Data mapping
All inverter i950 slave devices have a fixed generic data mapping. This data mapping enables the use of the slave devices with an i950 inverter as system bus master and with other EtherCAT-based master control systems (PLC).
–
The process data is set to 8 double words (32 bytes) for each direction.
 
–
Output data direction: From Master to Slave.
 
–
Output data: 0xA200:001 ... 0xA200:008
 
 
–
Input data direction: From Slave to Master.
 
–
Input data: 0xA680:001 ... 0xA680:008
 
 
–
This fixed data mapping is automatically activated as master for an i950 inverter.
 
–
The process data is transmitted cyclically in a 1 ms cycle between the master and the slaves.
 
–
The process data transfer is synchronised by the "Distributed Clocks" EtherCAT mechanism.
 
–
A i950 master device provides the DC master via the internal slave.
 
–
The data in the slaves is accepted synchronously with the PLC program in the master.
 
–
All slaves are synchronised with a reference clock, the so-called "DC master".
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0xA200:001
Systembus output data: Systembus data output 1
–
Read only
 
Generic system bus output data from the PLC to the inverter.
0xA200:002
Systembus output data: Systembus data output 2
–
Read only
 
0xA200:003
Systembus output data: Systembus data output 3
–
Read only
 
0xA200:004
Systembus output data: Systembus data output 4
–
Read only
 
0xA200:005
Systembus output data: Systembus data output 5
–
Read only
 
0xA200:006
Systembus output data: Systembus data output 6
–
Read only
 
0xA200:007
Systembus output data: Systembus data output 7
–
Read only
 
0xA200:008
Systembus output data: Systembus data output 8
–
Read only
 
0xA680:001
Systembus input data: Systembus data input 1
0 ... [0] ... 4294967295
Generic system bus input data from the inverter to the PLC.
0xA680:002
Systembus input data: Systembus data input 2
0 ... [0] ... 4294967295
0xA680:003
Systembus input data: Systembus data input 3
0 ... [0] ... 4294967295
0xA680:004
Systembus input data: Systembus data input 4
0 ... [0] ... 4294967295
0xA680:005
Systembus input data: Systembus data input 5
0 ... [0] ... 4294967295
0xA680:006
Systembus input data: Systembus data input 6
0 ... [0] ... 4294967295
0xA680:007
Systembus input data: Systembus data input 7
0 ... [0] ... 4294967295
0xA680:008
Systembus input data: Systembus data input 8
0 ... [0] ... 4294967295