Status LEDs

The meaning of the "RUN" and "ERR" LEDs can be obtained from the following two tables.
LED "RUN" (green)
Blinking pattern
EtherCAT status
Status/meaning
off
off / Init
The network option is not active at the network or is in the "Init" status.
blinking
Pre-Operational
Access to parameters and objects is possible.
No process data exchange.
Safe-Operational
The data is not active yet in the standard device.
on
"Operational"
Valid process data is exchanged cyclically.
"ERR" LED (red)
Blinking pattern
Status/meaning
off
No fault
flickers
Local error. The network option changes automatically to the "Safe-Operational" status.
on (red)
A "Sync Manager Watchdog Timeout" has occurred.
blinking
The configuration is invalid/incorrect.
 
"L/A" LED (green)
Blinking pattern
State
Meaning
off
Not connected
Network not available
on
Connected
Network available
No data transfer
blinking
Traffic
Data transfer