Setting
Please note when setting the parameters:
–
Defining the stop time:
 
–
Consider the closing time of the brake.
 
–
For applications without an encoder, the stop time must be 0.5 s longer than the deceleration time parameterized in the inverter.
 
 
 
The mode of action of the parameters can be found in the dialog box for the function in the "Safety parameter list" in the engineering tool used.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2894:001
SS1, SS2: Stopping time
0 ... [0] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Monitored stopping time for SS1 and SS2.
0x2895
SS1 Source SD-In
–
Safety parameter (+Safety parameter list+)
 
Selection of a safe input as a trigger source for the function.
0
Disabled
1
SD-In1
2
SD-In2
3
SD-In3
4
SD-In4
0x2896
SS1 Source S-Bus
–
Safety parameter (+Safety parameter list+)
 
Selection of the safety bus as the trigger source for the function.
0
Disabled
1
Activated
0x2897:001
SS1: Mode
–
Safety parameter (+Safety parameter list+)
 
Condition at which STO is triggered.
0
STO after stopping time
STO is only processed after the parameterized stopping time has elapsed.
1
STO at n=0
STO is already triggered after reaching n=0.
0x2897:002
SS1: Delay STO after n=0
0 ... [0] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Delay time after detection of n = 0 until triggering of STO
Only relevant if "SS1 mode" = "STO with n=0" and operation with encoder system.
0x2898
SS1 "SS1 active" - Output
–
Safety parameter (+Safety parameter list+)
 
Selection of the safe output for the "SS1 active" feedback.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic