Setting
Please note when setting the parameters:
–
Defining the stop time:
 
–
Consider the closing time of the brake.
 
 
–
Activate ramp monitoring.
 
–
Define the monitoring ramp:
 
–
Set the relative or absolute start offset of the ramp.
 
–
Set the smoothing time of the ramp.
The monitoring ramp is calculated from the start offset, smoothing time and stop time.
 
 
 
The mode of action of the parameters can be found in the dialog box for the function in the "Safety parameter list" in the engineering tool used.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2894:001
SS1, SS2: Stopping time
0 ... [0] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Monitored stopping time for SS1 and SS2.
0x2894:002
SS1, SS2: Ramp monitoring
–
Safety parameter (+Safety parameter list+)
 
Selection of whether the deceleration ramp is to be monitored when SS1 and SS2 are executed.
0
Disabled
1
Activated
0x2894:003
SS1, SS2: Ramp - Smoothing time
0 ... [0] ... 100 %
–
Safety parameter (+Safety parameter list+)
 
S-ramp time of the deceleration ramp for SS1 and SS2.
0 % = linear ramp
0x2894:004
SS1, SS2: Ramp - Offset mode
–
Safety parameter (+Safety parameter list+)
 
Definition of the speed offset at the start of ramp monitoring.
0
Relativ
1
Absolute
0x2894:005
SS1, SS2: Ramp - Start-offset relative
0 ... [5] ... 100 %
–
Safety parameter (+Safety parameter list+)
 
Definition of the speed offset at the start of ramp monitoring.
0x2894:006
SS1, SS2: Ramp - Start-offset absolute
0 ... [0] ... 16000 rpm
–
Safety parameter (+Safety parameter list+)
 
0x2894:007
SS1, SS2: Ramp - Currently monitored speed
–
Read only: x rpm
 
Currently monitored speed value with active ramp monitoring.
0x2894:008
SS1, SS2: Ramp - Minimum difference
–
Read only: x rpm
 
Minimum difference between actual speed and monitored ramp.
0x2895
SS1 Source SD-In
–
Safety parameter (+Safety parameter list+)
 
Selection of a safe input as a trigger source for the function.
0
Disabled
1
SD-In1
2
SD-In2
3
SD-In3
4
SD-In4
0x2896
SS1 Source S-Bus
–
Safety parameter (+Safety parameter list+)
 
Selection of the safety bus as the trigger source for the function.
0
Disabled
1
Activated
0x2897:001
SS1: Mode
–
Safety parameter (+Safety parameter list+)
 
Condition at which STO is triggered.
0
STO after stopping time
STO is only processed after the parameterized stopping time has elapsed.
1
STO at n=0
STO is already triggered after reaching n=0.
0x2897:002
SS1: Delay STO after n=0
0 ... [0] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Delay time after detection of n = 0 until triggering of STO
Only relevant if "SS1 mode" = "STO with n=0" and operation with encoder system.
0x2898
SS1 "SS1 active" - Output
–
Safety parameter (+Safety parameter list+)
 
Selection of the safe output for the "SS1 active" feedback.
0
Disabled
1
SD-Out1 positive logic
2
SD-Out1 negative logic