Diagnostics
Diagnostic parameter
Address
Name / setting range / [default setting]
Information
0x6041
CiA status word
–
Read only
 
Mappable CiA status word with bit assignment according to device profile CiA 402.
Bit  0
Ready to switch on
1 = drive ready to start
Bit  1
Switched on
1 = drive switched-on
Bit  2
Operation enabled
1 = operation enabled
Bit  3
Fault
1 = fault or trouble active
Bit  4
Voltage enabled
1 = DC bus ready for operation
Bit  5
Quick stop disabled
0 = quick stop active
Bit  6
Switch on disabled
1 = operation inhibited
Bit  7
Warning
1 = warning active
Bit  8
RPDOs disabled
1 = cyclic PDOs have been deactivated
Bit  9
CiA control enabled
1 = inverter can receive commands via network.
–
Bit is not set in the operating mode 0x6060 = "MS: Velocity mode [-2]".
 
Bit  10
Setpoint reached
1 = the actual speed is in the window.
Bit  11
Internal limit active
1 = internal limitation of a setpoint active
Bit  12
Operation mode specific
1 = operation enabled and no test mode activated. (no internal setpoint generation active.)
Bit  13
Operation mode specific
1 ≡ following error active
Bit  14
Brake released or switching
Bit  15
STO not active
0 = STO is active or impermissible state at the safe inputs SIA and SIB (inverter disabled)
1 = STO is not active (inverter enabled)