Quick stop
The quick stop function is used for stopping the axis and in the event of an error.
The ramp used can be set via the following parameters:
If the quick stop function is active, it is displayed in the status word of the technology application.
0x500A:005 Bit 13
0x500A:005 Bit 13The source for the signal for activating quick stop is set under the Application quick stop source parameter.
0x5020:007
0x5020:007Special features
–
The quick stop function starts with the acceleration "0".
Exception: If the axis is already in the deceleration phase, it is started with the active setpoint acceleration to avoid prolonging the existing braking process.
Exception: If the axis is already in the deceleration phase, it is started with the active setpoint acceleration to avoid prolonging the existing braking process.
–
Setpoint generation for the quick stop function starts at the actual speed.
–
During the deceleration it is changed to the speed-controlled operation.
–
After reaching standstill, it is changed to the position control.
–
During the stop, no torque reduction is effective.
Parameter