Control modes

With the default setting, the axis is always operated with activated speed control except the function used in the application requires a different control mode. 0x500A:090
The speed control is used if no motor encoder is available.
The speed control is used in the first homing phase during the search for the reference signal.
The speed control is used during deceleration with the quick stop function.
The active control type is displayed in the Active control mode parameter. 0x500A:091
 
Parameter
Address
Name / setting range / [default setting]
Information
0x500A:090
Default control mode
–
Setting can only be changed if the inverter is disabled.
 
0
Position control via motor encoder
1
Position control via load encoder
10
Speed control via motor encoder
0x500A:091
Actual control mode
–
Read only
 
0
Position control via motor encoder
1
Position control via load encoder
10
Speed control via motor encoder
20
Torque control
0x500A:092
Load encoder selection
–
Setting can only be changed if the inverter is disabled.
 
-
 
Encoder_Axis
0x500A:093
Position controller gain
0.0000 ... [20.0000] ... 214748.3647 1/s
0x500A:094
Load encoder output limit
0.0000 ... [100000.0000] ... 214748.3647
0x500A:095
Position controller output
–
Read only