External torque limits

Static torque limits can be defined for the axis, which are active during normal operation. The definition is done via the parameters:
–
Positive torque limit 0x500A:128
 
–
Negative torque limit 0x500A:129
 
The torque limits can be deactivated in the technology application and can be replaced by alternative torque limits.
The alternative torque limits are set in the technology application via a control word
in the inverter and via the L_MC1P_SetTorqueLimit function block in the Controller-based Automation.
If the set torque limits in the technology application have been changed, this is indicated in the Status word parameter in bit 20. 0x500A:005 Bit 20
The torque limits currently effective in the drive are displayed in the parameters Positive torque limit source and Negative torque limit source. 0x60E0 0x60E1