Product description

Product identification

This documentation applies to the Controller product family and consists of the following components and their identification:

 

Name of product and product ID

Name of product

Product ID

c430 controller

C43AE50xxxAxxxxxxx

c520 controller

C52AE10xxxAxxxxxxx

c550 controller

C55AE40xxxAxxxxxxx

c520 controller + Extended for customer - specific devices only

C52AE10xxxBxxxxxxx

C52AE10xxxCxxxxxxx

c550 controller + Extended for customer-specific devices only

C55AE40xxxBxxxxxxx

C55AE40xxxCxxxxxxx

This chapter describes the functions of the standard device (product ID CxxxxxxxxxAxxxxxxx) and the customer-specific variants (product IDs CxxxxxxxxxBxxxxxxx and CxxxxxxxxxCxxxxxxx). These are shown under "Controller cxx0 + Extended for customer specific - devices only" in engineering tools.

Location in the network

These components are located at the control level of the automation pyramid.. Furthermore, they are located in the security zone "CAP-Machine" Zones and conduits).

A diagram of a plant

Description automatically generated

Location in the network

The components addressed here have four relevant interfaces:

  • Conduit: Industrial Ethernet
    Between the controllers and the "Conduit: Industrial Ethernet" is the IoT gateway. Its task is to enable zone protection. If there is no IoT gateway in the system, the operator must ensure appropriate security at the zone border. This interface is not an open interface for direct connection to the Internet. The operator must take appropriate security measures to maintain the security zone.

  • Conduit: Fieldbus
    Fieldbus requires special consideration within cyber security. The fieldbuses are standardized and, in most cases, have no integrated security functions. Thus, this interface must be classified as SL-0 in the risk assessment of the operator.

  • Conduit: Engineering
    This conduit does not exist continuously, but only during commissioning or maintenance of the machine. Here, the system design must take into account in the risk assessment that the accesses are authorized and the employees have been instructed on the components and the machine cyber security concept. Furthermore, it must be ensured that the computer systems on which the necessary tools are installed comply with the current cyber security requirements and correspond to the state of cyber security.

  • Conduit: Field level
    This conduit connects the security zone "CAP Machine" with the "CAP Field". The special feature is in the cyber security consideration of the field components. These are connected via the communication medium EtherCAT and thus represent only a low level of protection in terms of cyber security. The operator must therefore ensure that no unauthorized access to the components can take place. This does not include any data technology or human access. This conduit thus enables a single data interface into the subordinate "CAP Field" security zone.

Intended purpose

The intended use of these components is described in the application as directed and can be found in the operating instructions for the respective component. In the following, some specifics regarding cyber security are discussed.

  • These components are professional equipment and may only be commissioned and decommissioned by specialists.

  • These components also require maintenance throughout their life cycle, which must be carried out by the operator.

  • Modifications to the firmware or hardware of the components are not permitted.

  • If these components are taken out of operation or disposed of, the instructions in this documentation must be observed.

  • Do not fit any unused optional modules (minimize attack surface).

Intended environment

The intended environment for these components is described in the application as directed and can be found in the operating instructions for the respective component. In the following, some specifics regarding cyber security are discussed.

  • These components must be mechanically protected against unauthorized use. This can be achieved, for example, via physical access control systems or lockable control cabinets. In this case, access may only be granted to authorized persons and the number of accesses should also be restricted.

  • In particular, SD Card may only be removed by users authorized by the operator.

  • The components are not operated directly on the open Internet, but must also be operated by the operator via protection systems such as firewall, IDS, IPS, … .

  • Deactivate all unused interfaces and/or protocols, both for the components mentioned here and for all components that are connected to the network.

  • The more security-critical an application is, the more systems should be separated. Only combine tasks on one component if they are in the same risk classification.

  • Wherever possible, use a Defense-in-Depth Concept in the environment of this component.

  • Use appropriate authentication mechanisms. This applies, for example, to passwords that have the necessary complexity and an appropriate life cycle. The current state of the art must be taken into account here.

  • Handle secrets, such as passwords, appropriately. The focus here is on the handling of secrets on the components noted here, but also on the data stored in the environment of these components.

  • Validate all input options for validity. Pay attention to all human user interfaces as well as the machine software interfaces.

  • Keep the installed firmware version up to date and install updates.

  • Evaluate the environment, the technical task to be performed and the existing component security in a security-critical consideration and assess whether additional protective measures are necessary for your application.

Security key indicators

Security key indicator (in accordance with IEC 62443-4-2):

  • These components are considered embedded devices (EDR).

  • These components have a security level of SL-C 0.

  • These components have an SL-vector from SL-C(Controller)={ IAC=0; UC=0; SI=0; DC=0; RDF=0; TRE=0; RA=0 }.