Option 1: Define network as standard setpoint source

If the setpoint is to be specified exclusively via the network, the network for the corresponding control can be simply set as the standard setpoint source.
–
Setting for the frequency control: 0x2860:001 (P201.01) = "Network [5]".
 
–
See the following table for settings for additional controls.
 
Control: size
Parameter
Setting
Further information
Frequency control: frequency setpoint
Network [5]
Frequency control Standard setpoint source 
PID control: reference value
Network [5]
PID control: feedback of the control variable (actual value)
Network [5]
PID control: speed feedforward control
Network [8]
Torque control: torque setpoint
Network [5]
Torque controlStandard setpoint source