Inverter diagnostics
The following parameters supply some information about the current operating status of the inverter.
This includes the following information:
–
Active access protection after log-in by means of PIN1/PIN2
–
Currently loaded parameter settings
–
Cause(s) for disable, quick stop and stop
–
Active control source and active setpoint source
–
Active operating mode
–
Status of the internal motor control
–
Keypad status
Some of the following parameters contain bit-coded status words. Each single bit has a certain meaning.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2040
(P197.00)
|
Access protection status
(Protect. status)
–
Read only
|
Bit-coded display of the active access protection after login by PIN1/PIN2.
|
|
|
Bit
0
|
No write access
|
||
|
Bit
1
|
Only favorites changeable
|
||
|
0x2827
(P198.00)
|
Currently loaded parameter settings
(Status load. par)
–
Read only
|
Display of the parameter settings currently loaded.
|
|
|
0
|
User settings
|
User parameter settings of the memory module
|
|
|
1
|
Reset 60 Hz setting
|
Delivery status (default setting) for 50-Hz device
|
|
|
2
|
Reset 50 Hz setting
|
Delivery status (default setting) for 60-Hz device
|
|
|
3
|
OEM default settings
|
OEM parameter settings of the memory module
|
|
|
0x282A:001
(P126.01)
|
Status words: Cause of disable
(Status words: Cause of disable)
–
Read only
|
Bit-coded display of the cause(s) for disabled inverter.
|
|
|
Bit
0
|
Flexible I/O configuration
|
1 = the inverter was disabled by the trigger set in 0x2631:001 (P400.01).
|
|
|
Bit
1
|
Network
|
1 = the inverter was disabled via network.
|
|
|
Bit
2
|
Axis command
|
1 = the inverter was disabled via axis command .
|
|
|
Bit
6
|
Fault DC-bus
|
1 = The inverter was disabled due to a DC-bus error.
|
|
|
Bit
7
|
Drive not ready
|
1 = the inverter was disabled internally since the drive was not ready for operation.
Possible causes:
–
Under/overvoltage in the DC bus
–
Defective device hardware
|
|
|
Bit
8
|
Quick stop active
|
1 = the inverter was disabled by the "Quick stop" function.
|
|
|
Bit
9
|
Motor data identification
|
1 = the inverter was disabled by the "Automatic identification of the motor data" function.
|
|
|
Bit
10
|
Holding brake
|
1 = the inverter was disabled by the "Holding brake control" function.
|
|
|
Bit
11
|
DC braking
|
-
1 = DC braking active.
|
|
|
Bit
12
|
CiA402 Inverter disabled
|
1 = the inverter was disabled by the internal state machine.
The bit is only set if
–
Operating mode 0x6060 (P301.00) = "CiA: Velocity mode (vl) [2]" and
–
state machine in the "Switch on disabled" state and
–
the state change has not been carried out via the "Disable operation" command.
|
|
|
Bit
13
|
CiA402 Quick stop option code 2
|
1 = the inverter was disabled by the "Quick stop" function.
|
|
|
Bit
14
|
Safety
|
1 = the inverter has been disabled by the integrated safety system.
|
|
|
Bit
15
|
CiA402 operation mode 0
|
1 = the inverter has been disabled because the selection "No selection [0]" is set in 0x6060 (P301.00).
|
|
|
0x282A:002
(P126.02)
|
Status words: Cause of quick stop
(Status words: Cause of QSP)
–
Read only
|
Bit coded display of the cause(s) of quick stop.
|
|
|
Bit
0
|
Flexible I/O configuration
|
1 = quick stop was activated by the trigger set in 0x2631:003 (P400.03).
|
|
|
Bit
1
|
Network
|
1 = quick stop was activated via network.
|
|
|
Bit
2
|
Axis command
|
1 = quick stop was activated via axis command 0x2822:003.
|
|
|
Bit
6
|
Error response
|
1 = quick stop has been activated as a response to an error.
|
|
|
0x282A:003
(P126.03)
|
Status words: Cause of stop
(Status words: Cause of stop)
–
Read only
|
Bit coded display of the cause(s) of stop.
|
|
|
Bit
0
|
Flexible I/O: Start disabled
|
1 = stop was activated by the trigger set in 0x2631:002 (P400.02).
|
|
|
Bit
1
|
Flexible I/O: Run forward
|
1 = stop has been activated due to cancellation of the command "Run forward (CW)".
|
|
|
Bit
2
|
Flexible I/O: Run reverse
|
1 = stop has been activated due to cancellation of the command "Run reverse (CCW)".
|
|
|
Bit
3
|
Flexible I/O: Jog forward
|
1 = stop has been activated due to cancellation of the command "Jog forward (CW)".
|
|
|
Bit
4
|
Flexible I/O: Jog reverse
|
1 = stop has been activated due to cancellation of the command "Jog reverse (CCW)".
|
|
|
Bit
5
|
Network
|
1 = stop was activated via network.
|
|
|
Bit
6
|
Keypad
|
1 = stop was activated via keypad.
|
|
|
Bit
7
|
Control mode transition
|
1 = stop has been activated due to a change of the operating mode.
|
|
|
Bit
8
|
End of sequence
|
1 = stop was activated by the "sequencer" function since the sequence is completed.
–
The bit is only set after the sequence is completed if End of sequence mode 0x402F (P824.00) is set ="Stop [1]" or "Stop and abort [2]".
|
|
|
Bit
9
|
Manual mode
|
1 = Stop was activated by the "Manual mode" function.
|
|
|
Bit
15
|
Waiting for start
|
1 = stop is active as a start command is not yet available (e. g. after enabling the inverter).
|
|
|
0x282A:004
|
Status words: Extended status word
–
Read only
|
Bit-coded status word.
|
|
|
Bit
8
|
Reverse rotational direction
|
1 = reversal active.
|
|
|
Bit
10
|
Inverter disabled (safety)
|
1 = The safety system integrated in the inverter has disabled the inverter/drive.
|
|
|
Bit
11
|
STO active
|
1 = "Safe Torque Off (STO)" safety function is active. Safe inputs SIA and SIB = LOW (simultaneously).
|
|
|
0x282A:005
(P126.05)
|
Status words: Device status
(Status words: Device status)
–
Read only
|
Display of the current inverter device state.
|
|
|
0
|
Initialisation
|
||
|
2
|
Not ready to switch on
|
||
|
3
|
Switch on disabled
|
||
|
4
|
Ready to switch on
|
||
|
5
|
Switched on
|
||
|
6
|
Operation enabled
|
||
|
7
|
Disable operation
|
||
|
8
|
Shut down
|
||
|
9
|
Quick stop active
|
||
|
10
|
Fault reaction active
|
||
|
11
|
Fault
|
||
|
0x282B:001
(P125.01)
|
Inverter diagnostics: Active control source
(Inverter diag.: Active control)
–
Read only
|
Display of the control source that is currently active.
|
|
|
0
|
Flexible I/O configuration
|
||
|
1
|
Network
|
||
|
2
|
Keypad
|
||
|
8
|
Keypad full control
|
||
|
9
|
Manual mode
|
||
|
0x282B:002
(P125.02)
|
Inverter diagnostics: Active setpoint source
(Inverter diag.: Active setpoint)
–
Read only
|
Display of the setpoint source that is currently active.
|
|
|
0
|
Not selected
|
||
|
1
|
Analog input 1
|
||
|
2
|
Analog input 2
|
||
|
3
|
Keypad Setpoint
|
||
|
4
|
HTL input
|
||
|
5
|
Network Setpoint
|
||
|
9
|
Manual mode: setpoint
|
||
|
11
|
Setpoint preset 1
|
||
|
12
|
Setpoint preset 2
|
||
|
13
|
Setpoint preset 3
|
||
|
14
|
Setpoint preset 4
|
||
|
15
|
Setpoint preset 5
|
||
|
16
|
Setpoint preset 6
|
||
|
17
|
Setpoint preset 7
|
||
|
18
|
Setpoint preset 8
|
||
|
19
|
Setpoint preset 9
|
||
|
20
|
Setpoint preset 10
|
||
|
21
|
Setpoint preset 11
|
||
|
22
|
Setpoint preset 12
|
||
|
23
|
Setpoint preset 13
|
||
|
24
|
Setpoint preset 14
|
||
|
25
|
Setpoint preset 15
|
||
|
31
|
Segment preset 1
|
||
|
32
|
Segment preset 2
|
||
|
33
|
Segment preset 3
|
||
|
34
|
Segment preset 4
|
||
|
35
|
Segment preset 5
|
||
|
36
|
Segment preset 6
|
||
|
37
|
Segment preset 7
|
||
|
38
|
Segment preset 8
|
||
|
39
|
Last segment
|
||
|
50
|
Motor potentiometer
|
||
|
51
|
PID setpoint
|
||
|
201
|
Internal value
|
Internal values of the manufacturer.
|
|
|
202
|
Internal value
|
||
|
203
|
Internal value
|
||
|
204
|
Internal value
|
||
|
205
|
Internal value
|
||
|
206
|
Internal value
|
||
|
0x282B:003
(P125.03)
|
Inverter diagnostics: Keypad LCD status
(Inverter diag.: Keypad LCD stat.)
–
Read only
|
Bit-coded state of the keypad status displays.
|
|
|
Bit
0
|
LOC
|
1 = local keypad control active.
|
|
|
Bit
1
|
REM
|
1 = remote control via terminals, network, etc. active.
|
|
|
Bit
2
|
MAN
|
1 = manual setpoint selection via keypad active.
|
|
|
Bit
3
|
Auto
|
1 = automatic setpoint selection via terminals, network, etc. active.
|
|
|
Bit
4
|
Set
|
1 = a parameter setting has been changed but not been saved yet in the memory module with mains failure protection
. |
|
|
0x282B:004
(P125.04)
|
Inverter diagnostics: Active drive mode
(Inverter diag.: Drive mode)
–
Read only
|
Display of the active drive mode.
|
|
|
0
|
Velocity mode
|
"Velocity mode" active.
|
|
|
1
|
PID control
|
PID control active.
|
|
|
2
|
Torque mode
|
"Torque mode" active.
|
|
|
4
|
Jog operation
|
"Jog forward (CW)" or "Jog reverse (CCW)" function active.
|
|
|
0x2831
|
Inverter status word
–
Read only
|
Bit coded status word of the internal motor control.
|
|
|
Bit
1
|
Speed setpoint 1 limited
|
1 = input of speed controller 1 in limitation.
|
|
|
Bit
2
|
Speed controller in limitation
|
1 = output of speed controller 1 in limitation.
|
|
|
Bit
3
|
Torque setpoint limited
|
1 = setpoint torque in limitation.
|
|
|
Bit
4
|
Q-current setpoint limited
|
1 = setpoint current in limitation.
|
|
|
Bit
5
|
Speed setpoint 2 limited
|
1 = input of speed controller
2 in "torque mode" in limitation. |
|
|
Bit
6
|
Upper speed limit active
|
||
|
Bit
7
|
Lower speed limit active
|
||
|
Bit
8
|
Flying restart active
|
-
|
|
|
Bit
10
|
Output frequency limited
|
1 = setpoint frequency with V/f operation in limitation.
|
|
|
Bit
11
|
Magnetization completed
|
1 = Magnetisation completed during V/f operation.
Otherwise 0.
|
|
|
Bit
12
|
Motor phase error
|
1 = motor phase failure detection active.
|
|
|
Bit
14
|
Error reset blocking time active
|
1 = the error can only be reset when the blocking time has elapsed.
|
|
|
0x2833
|
Inverter status word 2
–
Read only
|
Bit-coded status word 2 of the inverter.
|
|
|
Bit
1
|
Manual test mode active
|
1 = manual test mode active.
|
|
|
Bit
2
|
Manual control active
|
1 = manual control active.
|
|
|
Bit
6
|
DC braking active
|
1 = DC braking
active. |
|
|
Bit
15
|
UPS operation active
|
1 = UPS operation active.
|
|
|
0x293A
(P116.00)
|
Actual switching frequency
(Actual sw. freq.)
–
Read only
|
Display of the currently active switching frequency of the inverter.
Example:
–
"16 kHz variable / drive-optimised / 4 kHz min. [22]" is selected as switching frequency in 0x2939 (P305.00).
–
An increase of the ambient temperature and/or the load have caused a decrease of the switching frequency to 8 kHz. In this case, this parameter indicates the selection "8 kHz power loss-optimized [7]".
|
|
|
1
|
2 kHz drive-optimized
|
||
|
2
|
4 kHz drive-optimized
|
||
|
3
|
8 kHz drive-optimized
|
||
|
4
|
16 kHz drive-optimized
|
||
|
5
|
2 kHz power loss-optimized
|
||
|
6
|
4 kHz power loss-optimized
|
||
|
7
|
8 kHz power loss-optimized
|
||
|
8
|
16 kHz power loss-optimized
|
||
|
0x2DAC
(P119.00)
|
Keypad status
(Keypad status)
–
Read only
|
Bit-coded display of the keypad status.
|
|
|
Bit
0
|
Start Key
|
1 = keypad start key pressed.
|
|
|
Bit
1
|
Stop Key
|
1 = keypad stop key pressed.
|
|
|
Bit
2
|
Up arrow
|
1 = keypad up-arrow key pressed.
|
|
|
Bit
3
|
Down arrow
|
1 = keypad down-arrow key pressed.
|
|
|
Bit
4
|
Enter Key
|
1 = keypad enter key pressed.
|
|
|
Bit
5
|
Back key
|
1 = keypad back key pressed.
|
|
|
0x2DAD
(P120.00)
|
Internal hardware states
(Int. HW states)
–
Read only
|
Bit-coded display of internal hardware states.
|
|
|
Bit
0
|
Relay
|
0 = X9/NO-COM open and NC-COM closed.
1 = X9/NO-COM closed and NC-COM open.
|
|
|
Bit
1
|
Digital output 1
|
0 = LOW level, 1 = HIGH level.
|
|
|
Bit
2
|
Digital output 2
|
||
|
Bit
10
|
Charge Relay
|
1 = precharging of the DC bus via charge relay is active.
|
|
|
0x603F
(P150.00)
|
Error code
(Error code)
–
Read only
|
Error message
|
|
|
0x6061
(P788.00)
|
CiA: Active operation mode
(Act. op. mode)
–
Read only
|
CiA: Active operation mode
|
|
|
-2
|
MS: Velocity mode
|
Vendor specific velocity mode
|
|
|
-1
|
MS: Torque mode
|
Manufacturer-specific torque mode
|
|
|
0
|
No selection
|
No selection
|
|
|
2
|
CiA: Velocity mode (vl)
|
CiA: Velocity mode
|
|
Display of status words on keypad
Behaviour of the inverter in case of incompatible data in the memory module
pressed.
pressed.
pressed.
pressed.
pressed.
pressed.