Option 1: Define network as standard setpoint source
If the setpoint is to be specified exclusively via the network, the network for the corresponding control can be simply set as the standard setpoint source.
–
Setting for the frequency control: 0x2860:001 (P201.01) = "Network [5]".
–
See the following table for settings for additional controls.
|
Control: size
|
Parameter
|
Setting
|
Further information
|
|
Frequency control: frequency setpoint
|
Network [5]
|
Frequency control
Standard setpoint source |
|
|
PID control: reference value
|
Network [5]
|
Frequency control
Configuring the process controller |
|
|
PID control: feedback of the control variable (actual value)
|
Network [5]
|
||
|
PID control: speed feedforward control
|
Network [8]
|
||
|
Torque control: torque setpoint
|
Network [5]
|
Torque control
Standard setpoint source |
Standard setpoint source