PROFINET IO-Device

PROFINET® (Process Field Network) is a real-time capable network based on Ethernet.
 
–
PROFINET® is a registered trademark and patented technology licensed by the PROFIBUS & PROFINET International (PI) user organization.
 
–
Detailed information on PROFINET can be found on the web page of the user organization: www.profibus.com
 
–
PROFINET transmits, between the IO-Devices and a IO-Controller (PLC), parameter data, configuration data, diagnostic data, alarm messages, and process data.
 
–
The data is transmitted as a function of its time-critical behavior via corresponding communication channels.
 
–
The device is implemented as a PROFINET IO-Device in a PROFINET RT network.
 
–
The PROFINET connections are realized as standard RJ45 sockets.
 
 
Preconditions
–
In 0x231F:005 the network selection is set to "PROFINET".
 
–
The required GSDML device description files for PROFINET are installed in the engineering tool for configuring the network. 
 
 
Device description files for Lenze products can be found on the Internet:
www.Lenze.com 
à
Downloads
à
Product-related Application Knowledge Base articles
 
 
PROFINET connection
–
The controller is connected as an PROFINET IO-Device to an IO controller via the RJ45 sockets X396 (IN) and X397 (OUT).
 
–
An Ethernet cable CAT 5/5e, 2-pair with AWG22 (American Wire Gauge) or 4-pair with AWG22/24 is suitable for the connection.
 
More information about connections can be found on the Internet:
www.profibus.com 
à
PROFINET Cabling and Interconnection Technology
 
 
Typical topologies
Line
Tree
Ring
C
IO controller
SW
Switch SCALANCE (MRP capable)
D
IO device
R
Redundant domain
 
Bus-related information
Name
PROFINET RT
Communication medium
Ethernet 100 Mbps/s, full duplex
Application
Connection as a PROFINET-IO-Device
Status display
2 LEDs (BUS RDY, BUS ERR)
Connection designation
X396 (IN)
X397 (OUT)
 
Technical data
Communication profile
PROFINET
PNO identification number
0x0106
Device identification (Device ID)
Device-dependent:
–
Controller c430: 0xC430
 
–
Controller c520: 0xC520
 
–
Controller c550: 0xC550
 
Network topology
Line, tree, ring
Device
Type
IO device with real-time communication properties (RT)
Conformance Class B, NetloadClass III
Max. number
255
Per subnetwork
Address
Station name
Max. cable length
m
Not limited
The decisive factor is the length between the devices.
Max. cable length between two devices
m
100
Process data
–
Max. 244 PDOs: freely configurable, regardless of their direction (In, Out, In/Out)
 
–
Max. 1440 input bytes and max. 1440 output bytes
 
–
Scaling:
bytes: 1, 2, 4, 8, 12, 16, 24, 32, 48, 64, 80, 96, 128, 160, 192, 224, 250
Word: 1, 2, 4, 6, 8, 12, 16, 24, 32, 40, 48, 64, 80, 96, 112, 125
 
Cycle time
ms
1, 2, 3, 4, ...
Switching method
Cut-through
Optional functions
–
MRP (Media Redundancy Protocol)
 
–
Diagnostics
 
–
Acyclic services; parameter channel
 
–
Support I&M0..3
 
–
Exchangeable disk storage
 
Other data
Additional TCP/IP channel
 
Communication time
Communication time depending on
processing time in the controller
time between the start of a request and the arrival of the response
telegram runtime (transmission rate, telegram length)
nesting depth of the network
bus load
 
Processing time of process data
Update cycle
ms
1
In the controller
Processing time
ms
0 ... 1
Runtime of the application task of the technology application used (tolerance)
ms
1 ... x