Commissioning

Importing IO devices into the control configuration:
1.
Select the "Add device" command in the context menu of the target system (device, Lenze controller, ...) to extend the control configuration with the IO device.
 
2.
Name the inserted IO device sensibly.
You can enter a name by clicking on the element. The names must only contain the characters "A ... Z", "a ... z", "0 ... 9" or "_" and must not begin with a digit.
 
 
3.
Execute the "Add device" command in the context menu of the IO device.
 
4.
In the dialog box that appears, select the I/O modules to be used for the IO device and add it to the IO device by clicking the "Add device" button.
 
5.
Set the IP address, subnet mask, gateway address and the station name of the IO device in the PROFINET parameters (Fieldbus section).
 
 
Load the network configuration into the master:
1.
Log off: Menu command Online 
à
Log off or <Ctrl>+<F8>.
 
2.
Compile: Menu command "Build 
à
Compile" or <F11>.
 
3.
Log in: Menu command "Online 
à
Log in" or <Alt>+<F8>.
The configuration, the parameter settings and the PLC program are loaded into the IO controller. Afterwards, all IO devices are initialized.
These steps must be carried out after every change within the
»
PLC Designer
«
project. An already existing configuration and an existing PLC program in the IO controller will be then overwritten.