Settings in the Siemens »TIA Portal«

Here, commissioning with the Siemens »TIA Portal« is described. Please note that in the default setting of the Siemens »TIA Portal« changes of network parameters carried out by a Lenze engineering tool (e. g. »PLC Designer«) may be overwritten.
 
1.
Go to the device configuration and open the net view to drag the controller from the catalog to the net view of the PROFINET.
 
2.
Assign the controller to the associated IO-Controller.
 
3.
Mark the controller and change to the device view.
 
4.
Set the IP address and the station name ("PROFINET device name") in Properties.
See: Station name and IP configuration
In order that the controller can be identified via Ethernet when the IO controller is switched off, it is necessary that the station name and the IP configuration are saved in the device with mains failure protection via the separate entry with the Lenze engineering tool. 0x2022:003
 
 
5.
Below the device name and the name of the device description file, the device view shows the pre-assignment of the output and input process data words.
In Slot 1, pre-assigned process data words can be changed.
 
6.
Save the project in the engineering tool.
 
7.
Load the configuration into the IO-Controller.
 
8.
Set the IO-Controller to RUN.