Station name and IP configuration

The station name and the IP configuration can be assigned by the IO-Controller. These settings enable the IO-Controllerto identify the devices in the network and manage the data exchange.
The station name and the IP configuration can also be assigned by the »Engineering Tool«.
–
The station name of the IO device must be entered with permissible characters according to the PROFINET specification. 0x2381:004
 
–
Display of the currently used station name: 0x2382:004
 
–
The IP configuration comprises the assignments of:
 
–
IP address 0x2381:001
 
–
Subnet mask 0x2381:002
 
–
Gateway address 0x2381:003
 
 
–
Display of the actual IP configuration: 0x2382:001 ... 0x2382:003
 
Save the station name and the IP configuration in the IO Device with line voltage failure protection so the IO Device can be identified via PROFINET if the IO controller is switched off. 0x2022:003
 
An invalid station name or the assignment of invalid combinations of the IP address, subnet mask, and gateway address can have the consequence that no connection to PROFINET can be established.
In case of impermissible settings, the red LED "bus ERR" is blinking and the error message "PROFINET: Stack initialization error [0x8192]" is output.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2381:001
PROFINET settings: IP address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Set IP address
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 = 1).
 
0x2381:002
PROFINET settings: Subnet
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Set subnet mask
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 = 1).
 
0x2381:003
PROFINET settings: Gateway
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Set gateway address
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 = 1).
 
–
The gateway address is valid if the network address of the IP address is identical to the gateway address. In this case, no gateway functionality is used.
 
–
DHCP is not supported.
 
0x2381:004
PROFINET settings: Station name
["0"]
Set station name
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 = 1).
 
0x2381:005
PROFINET settings: I&M1 System designation
["0"]
Input/output of the I&M1 system designation
–
The default setting is an empty string.
 
0x2381:006
PROFINET settings: I&M1 Installation site
["0"]
Input/output of the I&M1 location identification code
–
The default setting is an empty string.
 
0x2381:007
PROFINET settings: I&M2 Installation date
["0"]
Input/output of the I&M2 date of installation
–
The default setting is an empty string.
 
0x2381:008
PROFINET settings: I&M3 additional information
["0"]
Input/output of the I&M3 additional information
–
The default setting is an empty string.