Suppress diagnostic messages to the IO controller

0x285A:001 serves to set which error response in the device suppresses the alarm message to the IO-Controller.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x285A:001
Diagnostic configuration: Alarm suppression
0 ... [0] ... 65535
Bit coded selection of error responses which suppress the alarm message to the IO controller.
–
Bit x = 1 = suppress alarm message.
 
–
In the default setting "0", an alarm message is displayed for all error responses.
 
Bit  0
Information
Bit  1
Warning
Bit  2
Warning locked
Bit  3
Trouble
Bit  4
Fault > Application quick stop > Quick stop